207740
VBG-PB-K30-D-S16
AS-Interface Gateway/Safety Monitor
The BW2087 is an AS-Interface double master specially designed for operation on the PCI bus, a bus system integrated in every modern PC. The plug and play properties of hardware and drivers allow the simultaneous operation of up to 4 masters and render manual configuration superfluous. An efficient event control enables the card to exchange data more quickly and increases the performance of the system considerably as a result. An interrupt is not essential, but supports the event control on a system level, which further improves the performance of the system. Gateway with integrated Safety Monitorfa. A switchable watchdog allows the monitoring of all communication between the AS-Interface master and the PC. If the PC operating system crashes, the AS-Interface master goes “offline” and all outputs are set as inactive. Extended diagnosis functions enable the localization of sporadically occurring configuration errors and the qualitative evaluation of ASInterface communication. Drivers are available for Windows 2000/XP. PLC functionality. The gateway is also available with optional PLC functionality.
| AS-Interface specification: | V3.0 |
| PLC-Functionality: | activateable |
| Duplicate address detection: | from AS-Interface slaves |
| Earth fault detection: | integrated |
| EMC monitoring: | integrated |
| Diagnostics function: | Extended function via display |
| Switch-on delay: | < 10 s |
| Response delay: | < 40 ms |
| UL File Number: | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
| Safety Integrity Level (SIL): | SIL 3 |
| Performance level (PL): | PL e |
| MTTFd: | 200 a |
| B10d: | 2 E+7 |
| Display: | Illuminated graphical LC display for addressing and error messages |
| LED PROFIBUS: | PROFIBUS master detected; LED green |
| LED AS-i ACTIVE: | AS-Interface operation normal; LED green |
| LED CONFIG ERR: | configuration error; LED red |
| LED PRG ENABLE: | autom. programming; LED green |
| LED POWER: | voltage ON; LED green |
| LED PRJ MODE: | projecting mode active; LED yellow |
| LED U AS-i: | AS-Interface voltage; LED green |
| LED AUX: | ext. auxiliary voltage UAUX ; LED green |
| LED EDM/Start: | External device monitoring circuit inputs closed, 4x yellow LEDs |
| LED output circuit: | Output circuit closed; 4 x green LEDs |
| Button: | 4 |
| Insulation voltage: | ≥ 500 V |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface; Output K3 and K4 24 V DC |
| Rated operating current: | ≤ 300 mA from AS-Interface |
| Interface type: | RS-485 |
| Protocol: | PROFIBUS DP V1 |
| Transfer rate: | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
| Interface type: | RS 232, serial Diagnostic Interface |
| Transfer rate: | 19,2 kBit/s |
| Interface type: | Chip card slot |
| Number/Type: | 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs) |
| Safety output: | Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3 ADC-13 at 30 VDC, 3 AAC-15 at 30 VAC Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5 ADC-13 at 30 VDC |
| PROFIBUS: | Sub-D interface |
| AS-Interface: | spring terminals, removable |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Electromagnetic compatibility: | EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | PROFIBUS according to DIN 19245 Part 3 |
| AS-Interface: | EN 62026-2:2013 |
| Standards: | EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e) |
| UL approval: | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
| Ambient temperature: | 0 ... 55 °C (32 ... 131 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP20 |
| Mass: | 800 g |
| Construction type: | Low profile housing , Stainless steel |
| ECCN: | |
| Kraj pochodzenia: | Deutschland |
| EAN: | 4050143025503 |
| Waga: | 0,95 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |