Pepperl+Fuchs 205988

VAR-KE3-TERM

AS-Interface repeater

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The Advanced-Repeater VAR-KE3-TERM galvanically separates two AS-Interface circuits, and conditions the AS-Interface signals electrically, which extends the cable length by 100 m. The Advanced-Repeater includes a Bus Termination, permitting a line extension of up to 200 m. The Bus Termination is switchable. Two repeaters can be cascaded, resulting in a maximum cable length of 300 m. With one Bus Termination included in line, the maximum circuit extension is up to approximately 600 m. AS-Interface advanced repeater with terminatorfa. The Advanced-Repeater features an alignment between sender and receiver that has been optimized even further and offers a shorter delay when the signals pass through the Advanced-Repeater. The Advanced-Repeater does not require any parameterisation and no own address in the AS-Interface; the overall number of slaves (31 or 62) per branch remains unchanged. The housing, only 22.5 mm in width, takes up little place in the switch cabinet. The module is mounted by snapping it on to the 35 mm mounting rail in keeping with European standard EN 50022. Pluggable screw terminals are used for connection. This method of mounting permits easy removal during initial operation or servicing. On account of the galvanic separation, each segment requires a power supply unit or a power extender. Two LEDs indicate the correct polarity of the AS-Interface cables; two LEDs indicate any communication errors in the respective AS-Interface circuits.

Parametry techniczne

AS-Interface specification: V3.0
Required master specification: ≥ V2.0
UL File Number: E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
MTTFd: 155 a
Switch: TERM ON/OFF switches the segment A terminator on/off
LED FAULT SEG A: Segment A error display; red LED red: communication error
LED FAULT SEG B: Segment B error display; red LED red: communication error
LED PWR SEG A: AS interface voltage segment A; green LED
LED PWR SEG B: AS-Interface voltage segment B; green LED
LED TERM: Segment A bus terminator switched on
LED U>26V: Segment A voltage > 26 V
LED U>18,5V: Segment A voltage > 18.5 V
Insulation voltage: ≥ 500 V
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: 60 mA (per strand element), 120 mA (total)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 EN 61000-6-3:2001 IEC 62026-2:2008
UL approval: An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient temperature: 0 ... 55 °C (32 ... 131 °F)
Storage temperature: -25 ... 75 °C (-13 ... 167 °F)
Degree of protection: IP20 according to EN 60529
Connection: removable terminals, terminal connection ≤ 2.5 mm2
Material: Housing: PA 66-FR
Mounting: DIN mounting rail

Parametry logistyczne

ECCN:
Kraj pochodzenia: TR
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m