Pepperl+Fuchs 200504

VAA-4E4A-G12-ZAL/EA2L

AS-Interface sensor/actuator module

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

G12 flat module. 4 inputs (PNP) and 4 electronic outputsfa. The VAA-4E4A-G12-ZA/EA2L is an AS-Interface trigger module with 4 inputs and 4 outputs. 2- and 3-wire sensors as well as mechanical contacts can be connected to the plus switching electronic inputs. The outputs are electronic outputs which can be energized with max. 24 V DC and 2 A per output. The solid housing permits fast mounting without tools as well as easy removal without tools. The stainless steel shell and the cast housing ensure durability and a high protection category. The connection to the AS-Interface calbe and to the external power supply is achieved via penetration technology in the integrated flat cable. The insert for the flat cables can be turned in two orientations. All connections to inputs and outputs are implemented via metal inserts for high stability. The connection to the sensors/actuators is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. The inputs and the connected sensors as well as the outputs and the connected actuators are supplied via an external power source (AUX). To indicate the current switching state there is an LED for each channel fitted to the top of the module. The outputs are protected against overload and short circuit, an output overload is indicated via an LED per channel. An LED to indicate the AS-Interface voltage and that the module has an address of 0 is available, another indicates errors in the AS-Interface communication as well as periphery faults. Another LED indicates the external power supply (AUX). This module can be mounted in any position using three screws or can be snapped onto the DIN rail using the stainless steel holder. An output overload is reported to the AS-Interface master via the function "periphery fault". The communcation with the AS-Interface remains intact.

Parametry techniczne

Slave type: Standard slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772
MTTFd: 180 a
Mission Time (TM): 20 a
Diagnostic Coverage (DC): 0 %
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching status (output); 4 yellow/red LEDs Yellow: output active Red: output overload
Auxiliary voltage (output): 24 V DC ± 15 % PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 40 mA
Protection class: III
Surge protection: UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Number/Type: 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Supply: from external auxiliary voltage UAUX
Current loading capacity: ≤ 600 mA overload and short-circuit resistant
Input current: ≤ 8 mA (limited internally)
Switching point: according to DIN EN 61131-2 (Type 2)
: 0 (unattenuated): ≤ 2 mA
: 1 (attenuated): ≥ 6 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 4 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Current: 2 A per output 6 A total (TB ≤ 40 °C) 4 A total (TB ≤ 70 °C)
Voltage: ≥ (UAUX - 0.5 V)
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005 EN 62026-2:2013
Profile: S-7.F
IO code: 7
ID code: F
ID1 code: F
ID2 code: E
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 OUT1
Electromagnetic compatibility: D1: IN2 OUT2
Electromagnetic compatibility: D2: IN3 OUT3
Electromagnetic compatibility: D3: IN4 OUT4
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Electromagnetic compatibility: P3: not used
Ambient temperature: -25 ... 70 °C (-13 ... 158 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 85 % , noncondensing
Climatic conditions: For indoor use only
Altitude: ≤ 2000 m above MSL
Shock and impact resistance: 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance: 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree: 3
Degree of protection: IP67
Connection: Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Material: Housing: PBT
Mass: 230 g
Tightening torque, cable gland: 0.4 Nm
Mounting: Mounting plate

Parametry logistyczne

ECCN:
Kraj pochodzenia: ID
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m