The slim-line power pack provides a direct voltage in an even larger adjustable output voltage range of 23 ... 30 V DC, while optimizing the space available in the control cabinet. Power supply, 24 to 30 V DC, 10 Afa. The current limit can be adjusted via an internal potentiometer. In addition to an LED showing the operational status (power), a red LED (overload) signals overloads on the output side. The connecting leads on the input side are safely covered with the plastic cover after installation. The device features a convenient DIN rail fastening.
| UL File Number: | E223176 |
| MTTFd: | 40 a |
| Mission Time (TM): | 10 a |
| Diagnostic Coverage (DC): | 0 % |
| LED Overload: | Red LED lights up for overload, flashes for hiccup mode |
| LED PWR: | LED green |
| Potentiometer: | Top: Output current limitation (covered by a dummy plug) Bottom: Output voltage adjustment |
| Fusing: | 6.3 AT |
| Capacity factor: | approx. 0.6 (Depending on input voltage) |
| Rated operating voltage: | 115/230 V AC (for 115 V range, jumper) Range: 93 to 132 V AC/187 to 265 V AC |
| Rated operating current: | 4.0 A (115 V) 1.9 A (230 V) |
| Supply frequency: | 47 ... 63 Hz |
| Efficiency: | approx. 89 % |
| Current limit: | approx. 12 A |
| Voltage: | 30 V ± 1 % Adjustment range 22.5 ... 29.5 V AC |
| Current: | 0 ... 10 A |
| Directive conformity: EMC Directive 89/336/EEC and Directive 2006/95/EC: | EN 55011, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 Klasse A, EN 61000-3-3, EN 60950 |
| Standard conformity: Electromagnetic compatibility: | EN 55011, EN 61000-6-1, EN 61000-6-2 |
| Standard conformity: Degree of protection: | EN 60529 |
| Standard conformity: Standards: | Harmonic waves: EN 61000-3-2 Class A Interference suppression: EN 55022, EN 55011 Class B Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge) Electromagnetic fields: IEC 61000-4-3 (10 V/m) Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled) Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical) Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz) |
| Ambient temperature: | -10 ... 70 °C (14 ... 158 °F) with free convection |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP20 |
| Protection class: | I, Protective conductor connection necessary |
| Connection: | Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
| Mass: | approx. 1200 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |