180048
VBA-1E3A-M18-ZE/E2-V1
AS-Interface sensor/actuator module
AS-Interface module in M18 stainless steel head ferrule. 1 input/3 outputsfa. The cylindrical AS-Interface module permits an easy connection of standard actuators to the AS-Interface. The input/output combination of 1:3 makes it particularly suitable for operation with motors (start/stop, forward/reverse, rotational speed 1/2, alarm indication); this means that all other actuators can also be easily connected to the AS-Interface. By means of mechanical adaptor nuts, the AS-Interface slave attaches to PG cable glands as well as metric cable glands. MOVIMOT® from SEW-Eurodrive requires an M25 adaptor with M18 x 1 quick disconnects which is included in the delivery package. The mechanically strong and short design is an advantage of the stainless steel head ferrule in welltried and tested Pepperl+Fuchs quality. The M12 plug establishes a connection to AS-Interface and to the auxiliary supply. Two LEDs show the voltage supply and AS-Interface communication errors. Using additional auxiliary power does not overload the AS-Interface power supply. Therefore, up to 31 cylinder modules can be connected to the AS-Interface line.
| Slave type: | A/B slave |
| AS-Interface specification: | V2.1 |
| Required master specification: | ≥ V2.0 |
| LED FAULT: | communication error / address is 0; LED red |
| LED PWR: | AS-Interface voltage; LED green |
| Auxiliary voltage (output): | 24 V DC ± 15 % PELV , not short-circuit protected |
| Insulation voltage: | ≥ 500 V |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 30 mA |
| Number/Type: | 1 Input for 2-wire sensor |
| Supply: | from external auxiliary voltage UAUX |
| Switching point: | OFF ≤ 0.8 mA ON ≥ 5 mA |
| Number/Type: | 3 electronic outputs, PNP |
| Supply: | from external auxiliary voltage UAUX |
| Current: | 20 mA per output |
| Electromagnetic compatibility: | acc. to EN 50081-2 / EN 50082-2 |
| Degree of protection: | EN 60529:2000 |
| AS-Interface: | EN 62026-2:2013 |
| Profile: | S-9.A.E |
| IO code: | 9 |
| ID code: | A |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| : D0: | - OUT1 |
| : D1: | - OUT2 |
| : D2: | - OUT3 |
| : D3: | IN1 - |
| Parameter bits (programmable via AS-i): | function |
| : P0: | not used |
| : P1: | not used |
| : P2: | not used |
| : P3: | not used |
| Ambient temperature: | 0 ... 70 °C (32 ... 158 °F) |
| Storage temperature: | -25 ... 70 °C (-13 ... 158 °F) |
| Shock and impact resistance: | ≤ 15 g at T ≤ 11 ms, 10 ... 55 Hz, 0,5 mm amplitude |
| Degree of protection: | IP67 according to EN 60529 The protection class appplies only for installation of the module in a connection housing for parts of the module located outside of the connection housing (external M12 connection, inside cable connection). The housing duct must be sealed with a suitable adhesive. |
| Connection: | AS-Interface and auxiliary voltage: M12x1 round connector auxiliary voltage, input and outputs: 20 cm connection cable |
| Mass: | 110 g |
| ECCN: | |
| Kraj pochodzenia: | Deutschland |
| EAN: | 4050143015290 |
| Waga: | 0,08 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |