121451
HiD2824
Switch Amplifier
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. 4-channel isolated barrier, 24 V DC supply (bus powered), Dry contact or NAMUR inputs, 4 relay contact outputs, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. The proximity sensor or switch controls two form A normally open relay outputs for the safe area load. The module output changes state when the input signal changes state. The normal output state can be reversed with the selector switches on the side of the unit. Line fault detection (LFD) can be selected or disabled via a selector switch. During an error condition, the relay reverts to its de-energized state and the LEDs indicate the fault. A separate fault output bus is available. The fault conditions can be monitored via a Fault Indication Board. This module mounts on a HiD Termination Board.
| Signal type: | Digital Input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | SL1: 1a(-), 1b(-); 2a(+), 2b(+) |
| Rated voltage: | 20.4 ... 30 V DC bus powered via Termination Board |
| Rated current: | 15 mA at 24 V, relay energized (per channel) |
| Power dissipation: | 0.35 W at 24 V (per channel) |
| Connection side: | field side |
| Connection: | SL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-) |
| Rated values: | acc. to EN 60947-5-6 (NAMUR) |
| Connectable sensor types: | potential free contact or proximity sensor |
| Switching point: | contact open 0.2 ... 1.2 mA, contact closed 2.1 ... 6.5 mA |
| Line fault detection: | breakage 0 ... 0.2 mA, short-circuit 6.5 mA ... maximum value |
| Connection side: | control side |
| Connection: | SL1: 8a, 7a; 10a, 9a; 10b, 9b; 8b, 7b |
| Output: | signal: relay SPST per channel, phase selectable |
| Response time: | 20 ms |
| Contact loading: | 50 V DC / 0.5 A non-inductive |
| Mechanical life: | 107 switching cycles |
| Connection: | SL1: 6b |
| Output type: | open collector transistor (internal fault bus) |
| Switching frequency: | < 10 Hz |
| Output/power supply: | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Output/Output: | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
| Display elements: | LEDs |
| Control elements: | DIP-switch |
| Configuration: | via DIP switches |
| Labeling: | space for labeling at the front |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Galvanic isolation: | EN 50178:1997 |
| Electromagnetic compatibility: | NE 21:2006 For further information see system description. |
| Degree of protection: | IEC 60529:2001 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Relative humidity: | 5 ... 90 %, non-condensing up to 35 °C (95 °F) |
| Degree of protection: | IP20 |
| Mass: | approx. 140 g |
| Dimensions: | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) |
| Mounting: | on Termination Board |
| Coding: | pin 1 and 2 trimmed For further information see system description. |
| EU-type examination certificate: | CESI 02 ATEX 086 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC |
| Electromagnetic compatibility: Input: | Ex ia, Ex iaD |
| Electromagnetic compatibility: Voltage: | 13.2 V |
| Electromagnetic compatibility: Current: | 20 mA |
| Electromagnetic compatibility: Power: | 66 mW |
| Supply: Maximum safe voltage: | 250 V AC (Attention! Um is no rated voltage.) |
| Certificate: | PF 11 CERT 2109 X |
| Supply: Marking: | II 3G Ex nA nC IIC T4 Gc |
| Galvanic isolation: Input/input: | safe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| CSA approval: Control drawing: | 366-005CS-12B (cCSAus) |
| IECEx approval: | IECEx TUN 04.0012 |
| CSA approval: Approved for: | [Ex ia] IIC |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |