Pepperl+Fuchs 116923

KFD2-FF-Ex2.RS232

RS 232 Repeater

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

This isolated barrier is used for intrinsic safety applications. It is a repeater for the bi-directional transfer of RS 232 signals. 1-channel isolated barrier, 24 V DC supply (Power Rail), RS 232 input/output, Transfer direction: to the control systempa. The input and output circuits are intrinsically safe and designed to transmit and receive RS 232 signals between the safe area and the hazardous area. This barrier accepts input signals in the ±3 V .. ±15 V range providing a nominal ±10 V output that is independent of the input voltage. The maximum rate of data exchange is 20 kBits per second.

Parametry techniczne

Signal type: Analog input
Connection: Power Rail or terminals 7+, 8-
Rated voltage: 19 ... 30 V DC
Rated current: approx. 40 mA
Power consumption: approx. 1.5 W
Interface: RS 232
Input: Connection: terminal 9
Input: Signal: logic 0: +3 ... +15 V logic 1: -3 ... -15 V
Output: Connection: terminal 11
Output: Signal: logic 0: +9 ... +12 V logic 1: -9 ... -12 V
Interface: RS 232
Input: Connection: terminals 2, 3
Input: Signal: logic 0: +3 ... +15 V logic 1: -3 ... -15 V
Output: Connection: terminals 1, 2
Output: Signal: logic 0: +9 ... +12 V logic 1: -9 ... -12 V
Output: Short-circuit current: max. 40 mA per channel
Display elements: LED
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 110 g
Dimensions: 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: BAS 02 ATEX 0116
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-40 °C ≤ Tamb ≤ 60 °C)
Electromagnetic compatibility: Equipment: terminals 1, 2, 3
Electromagnetic compatibility: Input: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Electromagnetic compatibility: Voltage: 19.9 V
Electromagnetic compatibility: Current: 75 mA
Electromagnetic compatibility: Power: 0.2 W
Electromagnetic compatibility: Internal capacitance: 0 F
Electromagnetic compatibility: Internal inductance: 0 H
Supply: Maximum safe voltage: 250 V rms on terminals 7, 9 and 11; 0 V on terminals 8, 10 and 12 and on Power Rail connector (Attention! The rated voltage can be lower.)
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012
UL approval: Control drawing: 116-0173 (cULus)
IECEx approval: IECEx certificate: IECEx BAS 05.0001
IECEx approval: IECEx marking: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m