112844
KFD2-PT2-Ex1-6-Y112844
Potentiometer Converter
1-channel, 24 V DC supply (Power Rail), Potentiometer input, Current output 0 mA ... 24 mA, Accuracy 0.05 %, Up to SIL 2 acc. to IEC 61508pa. Function. The transformer isolated barrier supplies power to the potentiometers in the hazardous area. The loop voltages are transmitted. The transformer isolated barrier is available with current and voltage outputs (terminals 7 and 8). It can be operated in the 3-, 4- or 5-wire mode with the potentiometer. In the 5-wire mode of operation, the potentiometer voltage is measured at terminals 2 and 5 and automatically readjusted. For a 4-wire connection on the transformer isolated barrier, terminals 4- and 5- are bridged. With the resistance adjustment on the front housing panel, it is possible to adjust the final value. For potentiometer resistances greater than 500 Ω, the potentiometer can be used to compensate for lead resistances up to 5 % of the potentiometer value. During adjustment, the potentiometer is set to 100 % of its value and the output signal is adjusted to 100 % of the required value. This adjustment can be repeated setting the potentiometer to 0 %. Terminals 4 and 5 as well as 1 and 2 must be bridged for a 3-wire connection to the potentiometer.
| Signal type: | Analog input |
| Safety Integrity Level (SIL): | SIL 2 |
| Connection: | Power Rail or terminals 11+, 12- |
| Rated voltage: | 20 ... 35 V DC |
| Ripple: | within the supply tolerance |
| Power dissipation: | 1 W |
| Power consumption: | 1.3 W |
| Connection side: | field side |
| Connection: | terminals 4-, 5-, 3+, 2+, 1+ |
| Potentiometer: Nominal resistance: | 500 Ω to 100 kΩ |
| Potentiometer: Supply voltage: | approx. 4.7 V |
| Lead resistance: | ≤ 5 % of the potentiometer resistance at ≥ 500 Ω (can be equalized by user) |
| Connection side: | control side |
| Connection: | terminals 7-, 8+ |
| Current output: | 0 ... 20 mA, load ≤1 kΩ |
| Accuracy: | 0.05 % |
| Deviation: Linearity: | ≤ ± 10 µA |
| Deviation: Influence of ambient temperature: | ≤ 1 µA/K |
| Rise time: | 10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms |
| Output/power supply: | functional insulation, rated insulation voltage 50 V AC |
| Control elements: | potentiometer |
| Configuration: | via potentiometer |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
| Electromagnetic compatibility: | NE 21:2006 |
| Degree of protection: | IEC 60529:2001 |
| Protection against electrical shock: | UL 61010-1 |
| Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
| Degree of protection: | IP20 |
| Connection: | screw terminals |
| Mass: | approx. 120 g |
| Dimensions: | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 |
| Mounting: | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate: | BAS 00 ATEX 7171 |
| Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
| Electromagnetic compatibility: Voltage: | 10.4 V DC |
| Electromagnetic compatibility: Current: | 46 mA |
| Electromagnetic compatibility: Power: | 120 mW |
| Supply: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
| Output: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
| Certificate: | TÜV 02 ATEX 1797 X |
| Output: Marking: | II 3G Ex nA II T4 |
| Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| FM approval: Control drawing: | 116-0129 |
| UL approval: Control drawing: | 116-0173 (cULus) |
| IECEx approval: IECEx certificate: | IECEx BAS 10.0060 IECEx BAS 10.0061X |
| IECEx approval: IECEx marking: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
| Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Optional accessories: | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03) |
| ECCN: | |
| Kraj pochodzenia: | SG |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |