112493
VBA-4E-G4-Pt100
AS-Interface analog module
The VBA-4E-G4-Pt100 analogue module has four analogue inputs for Pt100 RTDs. The asynchronous transformation of measured values and the data transfer is accomplished in accordance with AS-Interface profile 7.3. The resolution of the analogue values is 16 bit or 0.1 °C. System disturbances are eliminated using a programmable filter (50 Hz/60 Hz). G4 module IP65. 4 inputs for Pt100fa. The IP65 rated G4 module is especially suitable for use in hazardous environments. Connection to the measured-value transmitters is established by means of cable glands and cage tension spring terminals thus making the installation especially user-friendly. For preaddressing the module, it can be plugged directly onto the adapter of the hand-held programming device VBP-HH1. Various bases are available for the module. Use the U-G1F base to connect to the ASInterface flat cable, and the U-G1P base to connect to the round cable. The bases can, at the same time, be used as IP67 rated distributor box. Moreover, they both have two connection possibilities for AS-Interface cables. Output modules often have to be mounted in series with input modules. The outputs of the output modules are supplied externally with power. If the power is supplied via a flat cable, the power cable has to be mounted in the base of the input module. The U-G1FF base should be used in this case. The VBA-4E-G4-Pt100 then uses the AS-Interface cable instead of the power cable.
| Slave type: | Standard slave |
| AS-Interface specification: | V2.1 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 150 a at 30 °C |
| LED FAULT: | error display; LED red red: communication error red flashing: peripheral error |
| LED PWR: | AS-Interface voltage; LED green |
| LED ANALOG: | status of input signal; LED green off: not connected (peripheral error) green: signal within measurement range green flashing: signal outside of measurement range (peripheral error) |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 80 mA |
| Protection class: | III |
| Number/Type: | 4 inputs for Pt100, 2- or 3-wire connection |
| Supply: | from AS-Interface |
| Resolution: | 16 Bit / 0.1 °C |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| AS-Interface: | EN 62026-2:2013 |
| Profile: | S-7.3.E |
| IO code: | 7 |
| ID code: | 3 |
| ID2 code: | E |
| Data bits (function via AS-Interface): | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | mains power frequency filter P0=1, 50 Hz filter active P0=0, 60 Hz filter active |
| Electromagnetic compatibility: P1/P2: | Communication of the peripheral fault on measuring channels 1 to 4: [*PD-Z02313A*] |
| Electromagnetic compatibility: P3: | configuration Pt100 P3=1, 2-wire connection P3=0, 3-wire connection |
| Ambient temperature: | 0 ... 70 °C (32 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP65 |
| Connection: | cable piercing method or terminal compartment yellow flat cable or standard round cable inputs: M12 x 1.5 cable gland and cage tension spring terminals |
| Material: Housing: | PA 6 GF30 |
| Mass: | 350 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |