112480
VBA-2A-G4-U
AS-Interface analog module
G4 module IP65. 2 analog outputs (voltage)fa. The VBA-2A-G4-U analogue module has two voltage outputs 0 V .. 10 V. The asynchronous transformation of measured values and the data transfer is accomplished in accordance with AS-Interface profile 7.3. The measured-value transmitter can be supplied from the AS-Interface or from the external auxiliary power via the black flat cable, depending on the wiring of the plug-in jumpers. The resolution of the analogue values is 13 bit. The IP65 rated G4 module is especially suitable for rough conditions. Connection to the outputs is established by means of cable glands and cage tension spring terminals thus making the installation especially user-friendly. For pre-addressing the module it can be plugged directly onto the adapter of the hand-held programming device VBP-HH1. Both flat and round cables can be used for the connection of the AS-Interface transmission line and the external 24 V DC power supply. Use the U-G1FF base for the AS-Interface flat cable. The AS-Interface standardised EEMS interface, uses the cable piercing method to connect both the yellow and black flat cables. Use the U-G1PP base for a round cable. The AS-Interface cable as well as the external power supply may be connected within the U-G1PP base.
| Slave type: | Standard slave |
| AS-Interface specification: | V2.1 |
| Required master specification: | ≥ V2.1 |
| UL File Number: | E223772 |
| MTTFd: | 145 a at 30 °C |
| LED FAULT: | error display; LED red red: communication error red flashing: peripheral error |
| LED PWR: | AS-Interface voltage; LED green |
| LED ANALOG: | status output signal; LED green green: 0 V ≤ U ≤ 11.5 V green flashing: U > 11.5 V (peripheral error) |
| LED AUX: | ext. auxiliary voltage UAUX ; LED green |
| Auxiliary voltage (output): | 24 V DC ± 15 % PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 80 mA |
| Protection class: | III |
| Number/Type: | 2 analog outputs (voltage), 0 ... 10 V |
| Supply: | from AS-Interface or from external auxiliary voltage as required UAUX |
| Resolution: | 13 Bit / 1 mV |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 |
| Degree of protection: | EN 60529:2000 |
| AS-Interface: | EN 62026-2:2013 |
| Profile: | S-7.3.5 |
| IO code: | 7 |
| ID code: | 3 |
| ID2 code: | 5 |
| Data bits (function via AS-Interface): | The transfer of the data value is based on AS-Interface Profile 7.3. |
| Parameter bits (programmable via AS-i): | function |
| Electromagnetic compatibility: P0: | not used |
| Electromagnetic compatibility: P1: | projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected |
| Electromagnetic compatibility: P2: | Message of peripheral error P2=1, peripheral error is reported P2=0, peripheral error is not reported |
| Electromagnetic compatibility: P3: | not used |
| Ambient temperature: | 0 ... 70 °C (32 ... 158 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Degree of protection: | IP65 |
| Connection: | cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs: 2 x M16 x 1.5 cable glands and cage tension spring terminals, 1 x M12 x 1.5 cable gland (not used) |
| Material: Housing: | PA 6 GF30 |
| Mass: | 350 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,35 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |