KL9400
KL9400 | Power supply unit terminal for the K-bus
The KL9400 power supply unit terminal is used to refresh the K-bus. Data is exchanged between the Bus Coupler and Bus Terminal over the K-bus. Each Bus Terminal draws a certain amount of current from the K-bus (see “Current consumption K-bus” in the technical data). This current is fed into the K-bus by the relevant Bus Coupler’s power supply unit. The standard couplers (BKxx00, BCxx00) make 1.75 A available to the K-bus, while the “Economy” Couplers (BKxx10) and the “Low Cost” Couplers (LCxx00) provide 0.5 A. In configurations with a large number of Bus Terminals it is possible to use the KL9400 in order to supply an extra 2 A to the K-bus.
Input voltage: | 24 V DC (-15 %/+20 %) |
Output voltage: | 5 V DC |
Output current: | 2 A for K-bus supply |
Diagnostics: | – |
Current consumpt. K-bus: | – |
Power contacts: | 24 V DC max./10 A max. |
Short-circuit-proof: | yes |
Electrical isolation: | – |
Residual ripple: | – |
Weight: | approx. 65 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all KSxxxx Bus Terminals |
Approvals: | CE, UL, Ex, GL |