Article image EL3314-0010

Beckhoff EL3314-0010

EL3314-0010 | 4-channel thermocouple input terminal, high-precision, with open-circuit recognition

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The EL3314-0010 analog input terminal allows four thermocouples to be connected directly. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearisation across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal high-precision temperature measurement at the terminal. The EL3314-0010 can also be used for mV measurement.

Parametry techniczne

Number of inputs: 4
Power supply: via the E-bus
Thermocouple sensor types: types K, J, L, E, T, N, U, B, R, S, C (default setting type K), mV measurement
Distributed clocks:
Input filter limit frequency: typ. 1 kHz; depending on sensor length, conversion time, sensor type
Connection method: 2-wire
Resolution: 24 bit, presentation adjustable: 0.1/0.01/0.001 °C per digit or 10 nV per digit
Wiring fail indication: yes
Conversion time: approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Voltage measurement: ±78 mV (error: ±25 µV)
Temperature range: in the range defined in each case for the sensor (default setting: type K; -270…+1370 °C); voltage measurement: ±78 mV in 10 nV resolution
Measuring error: @ 50 Hz filter, @ 25 °C ambient temperature: type B: ±5.0 °C; type E: ±1.8 °C; type J: ±1.8 °C; type K: ±1.8 °C; type L: ±1.8 °C; type N: ±2.5 °C; type R: ±4.0 °C; type S: ±4.0 °C; type T: ±1.8 °C; type U: ±1.8 °C; type C: ±3.5 °C
Electrical isolation: 500 V (E-bus/signal voltage)
Current consumption power contacts:
Current consumption E-bus: typ. 200 mA
Special features: open-circuit recognition
Weight: approx. 60 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals/markings: CE, UL, ATEX
Ex-Marking: II 3 G Ex nA IIC T4 Gc

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m