Article image EL2634

Beckhoff EL2634

EL2634 | 4-channel relay output terminal 250 V AC/30 V DC

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The EL2634 output terminal has four relays, each of which has a single contact. The relay contact is suitable for use at up to 250 V AC or 30 V DC. The EtherCAT Terminal indicates its signal state by means of light emitting diodes. The EL2634 is equipped with potential-free contacts.

Parametry techniczne

Connection technology: relay output
Number of outputs: 4 x make contacts
Nominal voltage: 250 V AC/30 V DC
Load type: ohmic, inductive
Distributed clocks:
Ohmic switching current: 4 A AC/DC per channel
Inductive switching current: 2 A AC/DC per channel
Minimum permitted load: 0.1 mA at 0.1 V DC (at 120 operations/min.)
Lamp test, electronic ballast:
Current consumption E-bus: 80 mA
Electrical isolation: 500 V (E-bus/field potential)
Current consumption power contacts:
Bit width in the process image: 4 outputs
Operating cycles mech. (min.): 2 x 107 (at 18 x 103 switching cycles per hour)
Operating cycles electr. (min.): 1 x 105 (3 A/30 V DC ohmic load)
Configuration: no address or configuration setting
Weight: approx. 70 g
Operating/storage temperature: 0…+55 °C/-25…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Pluggable wiring: for all ESxxxx terminals
Approvals/markings: CE, UL

Parametry logistyczne

ECCN:
Kraj pochodzenia:
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m