YR20.246
MOSFET redundancy module
For N+1 and 1+1 redundant systems. Dual input with single output. Redundancy OK signal included, which reports the loss of redundancy. 160% (32.5A) Peak load capability. Reverse input polarity protection. Full power between -40°C and +70°C. Width only 32mm. Rugged metal housing. Easy wiring:. Distribution terminal for negative pole included
| Input Current: | 2*10A |
| Nominal Current Per Input: | 10A |
| DC-Input Voltage: | DC 24V-28V |
| Voltage Drop: | 110mV (H2) |
| Output Current: | 20A |
| Output Current Range: | 20A |
| Output Current Short circuit max.: | 26.00A |
| Size (WxHxD): | 32mm x 124mm x 117mm |
| Weight per Piece (excluding packing): | 310g |
| Operat. Temperature Range: | -40°C ... +70°C |
| Mounting Method: | Din-Rail |
| Power Losses, typ.: | 2.6W |
| Power Losses no Load: | 1.7W |
| Connection method: | screw terminals |
| H2): | 1+1 -redundancy (=50% of the nominal current) and symmetrical input currents |
| ECCN: | |
| País de origen: | |
| EAN: | |
| Peso: | 0,00 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |