302469
FB2203BR
Digital Output with Position Feedback
1 digital output, 2 digital inputs, Inputs and output Ex ia, Installation in suitable enclosures in Zone 1, Module can be exchanged under voltage (hot swap)pa
Occupied slots: | 1 |
Connection: | backplane bus |
Rated voltage: | 12 V DC , only in connection with the power supplies FB92** |
Power dissipation: | 1.4 W |
Power consumption: | 1.7 W |
Connection: | backplane bus |
Interface: | manufacturer-specific bus to standard com unit |
Number of channels: | 2 |
Sensor interface: Connection: | NAMUR sensor |
Sensor interface: Connection [2]: | volt-free contact |
Sensor interface: Connection [3]: | active binary signal 24 V DC |
Connection: | channel I: 2+, 5-; channel II: 3+, 6- |
Rated values: | acc. to EN 60947-5-6 (NAMUR) |
Switching point/switching hysteresis: | 1.2 ... 2.1 mA / ± 0.2 mA |
Internal resistor: | 1 kΩ |
Line fault detection: | can be switched on/off for each channel via configuration tool |
Sensor interface: Connection: | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring |
Sensor interface: Short-circuit: | < 360 Ω |
Sensor interface: Open-circuit: | < 0.35 mA |
Minimum pulse duration: | 1 ms |
Number of channels: | 1 |
Suitable field devices: Field device: | Solenoid Valve |
Suitable field devices: Field device [2]: | audible alarm |
Suitable field devices: Field device [3]: | visual alarm |
Connection: | channel I: 1+, 4- |
Open loop voltage: | 24 V |
Current limit: | 50 mA |
Internal resistor: | 360 Ω |
Line fault detection: | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) |
Suitable field devices: Short-circuit: | < 145 Ω |
Suitable field devices: Open-circuit: | > 2 kΩ |
Response time: | 20 ms (depending on bus cycle time) |
Watchdog: | within 0.5 s the device goes in safe state, e.g. after loss of communication |
LED indication: | LED green: supply LED red: output line fault LED yellow: status output |
Coding: | optional mechanical coding via front socket |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1 |
Electromagnetic compatibility: | NE 21 |
Degree of protection: | IEC 60529 |
Environmental test: | EN 60068-2-14 |
Shock resistance: | EN 60068-2-27 |
Vibration resistance: | EN 60068-2-6 |
Damaging gas: | EN 60068-2-42 |
Relative humidity: | EN 60068-2-56 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity: | 95 % non-condensing |
Shock resistance: | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance: | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas: | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Degree of protection: | IP20 (module) , a separate housing is required acc. to the system description |
Connection: | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
Mass: | approx. 350 g |
Dimensions: | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) |
EU-Type Examination Certificate: | PTB 97 ATEX 1074 U |
Electromagnetic compatibility: Marking: | II 2(1) G Ex d [ia Ga] IIC Gb |
Input: Voltage: | 14.1 V |
Input: Current: | 16 mA |
Input: Power: | 55 mW (linear characteristic) |
Input: Internal capacitance: | 1.65 nF |
Output: Voltage: | 27.83 V |
Output: Current: | 91.7 mA |
Output: Power: | 636 mW |
Output: Internal capacitance: | 1.65 nF |
Galvanic isolation: Input/power supply, internal bus: | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Galvanic isolation: Output/power supply, internal bus: | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 |
ATEX approval: | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U |
EAC approval: | Russia: RU C-IT.MIII06.B.00129 |
Marine approval: Lloyd Register: | 15/20021 |
Marine approval: DNV GL Marine: | TAA0000034 |
Marine approval: American Bureau of Shipping: | T1450280/UN |
Marine approval: Bureau Veritas Marine: | 22449/B0 BV |
System information: | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. |
Supplementary information: | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
ECCN: | |
País de origen: | Deutschland |
EAN: | 4050143070008 |
Peso: | 0,55 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |