269780
VAA-4E4A-KE5-ZEJQ/R
AS-Interface sensor/actuator module
Cabinet module. 4 inputs and 4 relay outputsfa
| Slave type: | Standard slave |
| AS-Interface specification: | V3.0 |
| Required master specification: | ≥ V2.0 |
| UL File Number: | E223772 |
| MTBF: | 224 a |
| LED FAULT: | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
| LED INT: | Internal input supply active; LED green |
| LED PWR: | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| LED IN: | switching state (input); 4 LED yellow |
| LED OUT: | Switching state (output); 4 LED yellow |
| Auxiliary voltage (input): | 12 ... 30 V DC PELV |
| Rated operating voltage: | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current: | ≤ 35 mA (without sensors) / max. 230 mA |
| Surge protection: | O1 ... O4: Over voltage category II UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV) |
| Number/Type: | 4 inputs for 3-wire sensors (PNP), DC |
| Supply: | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
| Voltage: | 21 ... 31 V DC (INT) |
| Current loading capacity: | ≤ 150 mA, overload- and short-circuit protected (INT) |
| Input current: | ≤ 5.6 mA (max.) |
| Switching point: | according to DIN EN 61131-2 (type 1) |
| : 0 (unattenuated): | ≤ 0.5 mA |
| : 1 (attenuated): | ≥ 2 mA |
| Signal delay: | < 1 ms (input/AS-Interface) |
| Number/Type: | 4 relay outputs, normally open |
| Supply: | none |
| Nominal load: Per contact: | 2 A/30 VDC; 2 A/250 VAC For more information, see the "Galvanic Isolation" section |
| Nominal load: Per module: | 8 A |
| Control circuit: | ≤ 11 mA per relay (from AS-Interface) |
| Switching delay: | < 10 ms (AS-Interface/contact) |
| Usage category: | DC-13 and AC-14 |
| Switching: Mechanical: | 5 x 107 |
| Switching: Electrical: | 2 x 105 (250 VAC, 2 A, cos φ = 0.4) |
| Input/Output: | safe isolation, Rated insulation voltage 252 Veff |
| Input/AS-Interface: | Switch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff |
| Output/Output: | Basic insulation, rated insulation voltage 250 Veff, in phase |
| Output/AS-Interface: | safe isolation, Rated insulation voltage 252 Veff |
| Electromagnetic compatibility: Directive 2014/30/EU: | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Low voltage: Directive 2006/95/EC: | EN 60664-1:2007 |
| Galvanic isolation: | EN 60664-1:2007 |
| Degree of protection: | EN 60529:2000 |
| Fieldbus standard: | EN 62026-2:2013 |
| Electrical safety: | IEC 61140:2009 |
| Input: | EN 61131-2:2004 |
| Emitted interference: | EN 61000-6-4:2007 |
| AS-Interface: | EN 62026-2:2013 |
| Noise immunity: | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013 |
| Profile: | S-7.0 |
| IO code: | 7 |
| ID code: | 0 |
| ID1 code: | F |
| ID2 code: | E |
| Data bits (function via AS-Interface): | input output |
| Low voltage: D0: | IN1 O1 |
| Low voltage: D1: | IN2 O2 |
| Low voltage: D2: | IN3 O3 |
| Low voltage: D3: | IN4 O4 |
| Parameter bits (programmable via AS-i): | function |
| Low voltage: P0: | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| Low voltage: P1: | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
| Low voltage: P2: | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
| Low voltage: P3: | not used |
| Ambient temperature: | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature: | -25 ... 85 °C (-13 ... 185 °F) |
| Relative humidity: | 85 % , noncondensing |
| Climatic conditions: | For indoor use only |
| Altitude: | ≤ 2000 m above MSL |
| Shock and impact resistance: | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Vibration resistance: | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Pollution degree: | 2 |
| Degree of protection: | IP20 Installation in an enclosure with a minimum protection class of IP54 required |
| Connection: | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
| Material: Housing: | PA 66-FR |
| Mass: | 125 g |
| Mounting: | DIN mounting rail |
| ECCN: | |
| País de origen: | Singapur |
| EAN: | 4050143046560 |
| Peso: | 0,16 kg |
| Longitud: | 0,00 m |
| Anchura: | 0,00 m |
| Altura: | 0,00 m |