Descripción

4-channel, Outputs Ex ic, Installation in Zone 2 and safe area, Line fault detection (LFD)pa

Parámetros técnicos

Occupied slots: 2
Connection: backplane bus / booster terminals
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Input voltage range: 18.5 ... 32 V DC (SELV/PELV) booster voltage
Power dissipation: 3 W
Power consumption: 0.15 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 4
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-
Current limit: 37 mA
Internal resistor: max. 370 Ω
Open loop voltage: 24.5 V
Line fault detection: can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Suitable field devices: Short-circuit: < 100 Ω
Suitable field devices: Open-circuit: > 15 kΩ
Response time: 10 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
Reaction time: 10 s
LED indication: Power LED (P) green: supply Status LED (I) red: line fault , red flashing: communication error
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 150 g
Dimensions: 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Output: Voltage: 27.8 V
Output: Current: 90.4 mA
Output: Power: 629 mW
Output: Internal capacitance: 1.65 nF
Output: Internal inductance: 0 mH
Certificate: PF 08 CERT 1234 X
Output: Marking: II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
IECEx approval: BVS 09.0037X
Directive conformity: Approved for: Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
Marine approval: Lloyd Register: 15-20021
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parámetros logísticos

ECCN:
País de origen: Deutschland
EAN: 4050143064076
Peso: 0,18 kg
Longitud: 0,00 m
Anchura: 0,00 m
Altura: 0,00 m