TY7439
Evaluation unit with display for PT100/PT1000 temperature sensors. TR-000KDBM12-QFPKG/US/
Number of inputs and outputs: | Number of digital outputs: 2 |
Measuring range [°C]: | -100...600 |
Process connection: | threaded connection G 1/2 external thread |
Special feature: | Gold-plated contacts |
Application: | for Pt100 and Pt1000 measuring elements |
Operating voltage [V]: | 18...32 DC; ("supply class 2" to cULus) |
Current consumption [mA]: | < 50 |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 1 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital outputs: 2 |
Total number of outputs: | 2 |
Output signal: | switching signal; IO-Link; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 250 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range [°C]: | -100...600 |
Set point SP [°C]: | -99.8...600 |
Reset point rP [°C]: | -100...599.8 |
In steps of [°C]: | 0.1 |
Resolution of switching output [K]: | 0.1 |
Resolution of display [K]: | 0.1 |
Switch point accuracy [K]: | ± 0,3 + (± 0,1 % MS) |
Display accuracy [K]: | ± 0,3 + (± 0,1 % MS) |
Temperature coefficient [% of the span / 10 K]: | 0,1; (in case of deviation from the reference condition 25 °C) |
Response time [ms]: | 390 |
Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
Ambient temperature [°C]: | -25...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 67 |
EMC: | DIN EN 61000-6-3 DIN EN 61000-6-2 |
Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
DIN IEC 68-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 252 |
UL approval: | UL Approval no. K012 |
UL Approval no.: | K012 |
Weight [g]: | 190 |
Materials: | stainless steel (1.4301 / 304); EPDM/X; PC; PBT; FPM |
Process connection: | threaded connection G 1/2 external thread |
Display: | Display unit 1 x LED, green switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit |
Display unit: | 1 x LED, green |
switching status: | 2 x LED, yellow |
measured values: | alphanumeric display, red/green 4-digit |
Remarks: | MS = set measuring span |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
País de origen: | US |
EAN: | |
Peso: | 0,19 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |