EP9224-0023
EP9224-0023 | 4/4-channel power distribution for EtherCAT Box modules with current measurement/data logging
The EP9224-0023 enables connection of four EtherCAT Box power supply branches. In each 24 V branch the current consumption for the control voltage U. S, and the peripheral voltage U. P, is monitored, limited, and, if necessary, switched off.
Number of outputs: | 4 x M8, 4-pin (per US/UP) |
Connection method: | M8, 4-pin |
Max. output current: | per M8: 4 A per US and UP |
Load type: | EtherCAT Box modules |
Infeed: | plug 7/8", max. 16 A per US/UP |
Power feed through: | socket 7/8", max. 16 A per US/UP |
Signalling contact: | potential-free make contact, M8 |
Nominal voltage: | 24 V DC (-15 %/+20 %) |
Distributed clocks: | – |
Bus interface: | 2 x M8 socket, shielded, screw type |
Protocol: | EtherCAT |
Electrical isolation: | 500 V |
Data logging: | recording of relevant data in case of failure |
Special features: | input voltages/currents, output currents via process data |
Weight: | approx. 165 g |
Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 65/66/67 (conforms to EN 60529)/variable |
Approvals: | CE, UL in preparation |
ECCN: | |
País de origen: | |
EAN: | |
Peso: | 0,00 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |