EL2732
EL2732 | 2-channel triac output terminal
The EL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two independent outputs and indicates its signal state by means of light emitting diodes.
Connection technology: | triac output, 2-wire |
Number of outputs: | 2 x make contacts (without power contacts), mutually locked |
Rated load voltage: | 12…230 V AC |
Load type: | ohmic, inductive |
Distributed clocks: | – |
Max. output current: | 0.5 A |
Switching times: | in zero crossing, 0.1…10 ms |
Frequency range: | 47…63 Hz |
Surge voltage protection: | > 275 V |
Peak current: | 40 A (16 ms), 1.5 A (30 s) |
Standby current: | 0.6 mA |
Leakage current (OFF state): | typ. 0.8 mA, max. 1.5 mA |
Switch-on time: | 0.1…10 ms, zero crossing |
Switch-off time: | T/2 |
Max. residual voltage: | 1.5 V (60 mA…1 A), 150 Ω (< 60 mA) |
Current consumption E-bus: | typ. 120 mA |
Electrical isolation: | 500 V (E-bus/field voltage), 3750 V AC (1 min.) |
Current consumption power contacts: | – |
Bit width in the process image: | 2 outputs |
Configuration: | no address or configuration setting |
Special features: | suitable for conventional blind motors |
Weight: | approx. 55 g |
Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
Relative humidity: | 95 %, no condensation |
Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos.: | IP 20/variable |
Pluggable wiring: | for all ESxxxx terminals |
ECCN: | |
País de origen: | |
EAN: | |
Peso: | 0,00 kg |
Longitud: | 0,00 m |
Anchura: | 0,00 m |
Altura: | 0,00 m |