2320283
QUINT4-UPS/1AC/1AC/1KVA
| Width: | 290 mm |
| Height: | 130 mm |
| Depth: | 125 mm |
| Installation distance right/left: | 5 mm / 5 mm |
| Installation distance top/bottom: | 50 mm / 50 mm |
| Degree of protection: | IP20 |
| Ambient temperature (operation): | -25 °C ... 60 °C (> 50 °C Derating: 2.5 %/K) |
| Ambient temperature (storage/transport): | -40 °C ... 85 °C (with charged energy storage device) |
| Max. permissible relative humidity (operation): | ≤ 95 % |
| Climatic class: | 3K3 (EN 60721) |
| Installation height: | ≤ 3000 m (> 2000 m, observe derating) |
| Nominal input voltage: | 100 V AC -10 % / +20 % |
| Input voltage range: | 90 V AC ... 264 V AC |
| AC frequency range: | 45 Hz ... 65 Hz |
| Buffer period: | 1 h (38 AH) |
| Permissible backup fuse: | B16 230 V AC |
| Power factor (cos phi): | 0.9 |
| Nominal output voltage: | 100 V AC |
| Nominal output current (IN): | 7.8 A (100 V AC) |
| POWER BOOST (IBoost): | 13 A (120 V AC) |
| Derating: | > 50 °C ... 60 °C (2.5%/K) |
| Connection in parallel: | Yes, 2 |
| Connection in series: | No |
| Maximum power dissipation in no-load condition: | typ. 17 W (120 V AC) |
| Net weight: | 5 kg |
| Efficiency: | > 92 % (120 V AC) |
| MTBF (IEC 61709, SN 29500): | 217546 h (230 V AC, at 40 °C) |
| Degree of protection: | IP20 |
| Protection class: | I |
| Connection method: | Screw connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 6 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 4 mm² |
| Conductor cross section AWG min.: | 30 |
| Conductor cross section AWG max.: | 10 |
| Stripping length: | 8 mm |
| Connection method: | Screw connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 6 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 4 mm² |
| Conductor cross section AWG min.: | 30 |
| Conductor cross section AWG max.: | 10 |
| Stripping length: | 8 mm |
| Connection method: | Screw connection |
| Conductor cross section solid min.: | 0.2 mm² |
| Conductor cross section solid max.: | 2.5 mm² |
| Conductor cross section flexible min.: | 0.2 mm² |
| Conductor cross section flexible max.: | 2.5 mm² |
| Conductor cross section AWG min.: | 30 |
| Conductor cross section AWG max.: | 12 |
| Stripping length: | 8 mm |
| Standard designation: | Uninterruptible power supply systems |
| Standards/regulations: | EN 62040-1 |
| Electromagnetic compatibility: | Conformance with EMC Directive 2014/30/EU |
| Low Voltage Directive: | Conformance with Low Voltage Directive 2014/35/EC |
| Electrostatic discharge: | EN 61000-4-2 |
| Contact discharge: | ± 6 kV |
| Discharge in air: | ± 8 kV |
| Electromagnetic HF field: | EN 61000-4-3 |
| Frequency range: | 80 MHz ... 6 GHz |
| Test field strength: | 10 V/m |
| Comments: | Criterion A |
| Fast transients (burst): | EN 61000-4-4 |
| Input: | ± 2 kV |
| Output: | ± 2 kV |
| Signal: | ± 2 kV |
| Comments: | Criterion A (B for USB) |
| Surge voltage load (surge): | EN 61000-4-5 |
| Signal: | 1 kV (asymmetrical) |
| Comments: | Criterion A |
| Conducted interference: | EN 61000-4-6 |
| Frequency range: | 0.15 MHz ... 80 MHz |
| Voltage: | 10 V |
| Comments: | Criterion A |
| Power frequency magnetic field: | EN 61000-4-8 |
| Frequency: | 50 Hz |
| Test field strength: | 100 A/m |
| Comments: | Criterion A |
| Criterion A: | Normal operating behavior within the specified limits. |
| Criterion B: | Temporary impairment to operational behavior that is corrected by the device itself. |
| REACh SVHC: | Lead 7439-92-1 |
| eCl@ss 10.0.1: | 27040705 |
| eCl@ss 5.1: | 27040603 |
| eCl@ss 6.0: | 27040600 |
| eCl@ss 7.0: | 27040602 |
| eCl@ss 8.0: | 27040602 |
| eCl@ss 9.0: | 27040705 |
| ETIM 5.0: | EC000382 |
| ETIM 6.0: | EC000382 |
| ETIM 7.0: | EC000382 |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 5,53 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |