Pepperl+Fuchs 326146

VBA-4E3A-G20-ZEL/E2L-P11

AS-Interface I/O module

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The AS-Interface I/O module VBA-4E3A-G20-ZEL/E2L-P* is a field module with 4 inputs for 3-wire sensors and 3 electronic outputs. The outputs are overload and short-circuit protected. G20 module for digital inputs/outputs, 4 inputs and 3 outputsfa. The compact housing can be installed directly in support profiles or conduits. The connection to the AS-Interface network and power supply is made using the AS-Interface flat cable and insulation piercing technology. The pivoted flat cable guide is secured using a snap-fit. No tools are required. The inputs and outputs are connected via cable outputs with M12 round plug connectors. Power for the inputs and outputs is provided by the external auxiliary voltage UAUX. The current switching state of the inputs and outputs is indicated by the IN and OUT LEDs. The PWR and FAULT LEDs indicate the status of the AS-Interface (normal operation, communication error, peripheral fault, address 0). The AUX LED indicates the external power supply. Notes:. The communication monitor of the module deactivates the outputs if the AS-Interface does not communicate with the module for more than 40 ms. A signal indicating an overload of the outputs or the input supply or the absence of the external auxiliary voltage is also transmitted to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues.

Parametry techniczne

Slave type: A/B slave
AS-Interface specification: V3.0
Required master specification: ≥ V2.1
UL File Number: E223772 "For use in NFPA 79 Applications only"
MTBF: 110 a
LED FAULT: error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED PWR: AS-Interface voltage; green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED AUX: ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage
LED IN: switching state (input); 4 LED yellow
LED OUT: Switching state (output); 3 LED yellow
Auxiliary voltage (output): 20 ... 30 V DC PELV
Rated operating voltage: 26.5 ... 31.6 V from AS-Interface
Rated operating current: ≤ 35 mA
Number/Type: 4 Inputs for 3-wire sensors (PNP), DC
Supply: from external auxiliary voltage UAUX
Current loading capacity: 500 mA , overload and short-circuit protected
Input current: ≤ 8 mA (limited internally)
Switching point: according to DIN EN 61131-2 0 (undamped) ≤ 0.5 mA 1 (damped) ≥ 2.0 mA
Signal delay: < 1 ms (input/AS-Interface)
Number/Type: 3 electronic outputs, PNP, overload and short-circuit proof
Supply: from external auxiliary voltage UAUX
Voltage: ≥ (UAUX - 0.5 V)
Current: 2 A per output TB ≤ 40 °C: 6 A total TB ≤ 60 °C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
Electromagnetic compatibility: Directive 2014/30/EU: EN 62026-2:2013
Degree of protection: EN 60529:2000
Fieldbus standard: EN 62026-2:2013
Input: EN 61131-2:2007
Emitted interference: EN 61000-6-4:2007
AS-Interface: EN 62026-2:2013
Noise immunity: EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Profile: S-7.A.E
IO code: 7
ID code: A
ID1 code: 7
ID2 code: E
Data bits (function via AS-Interface): input output
Electromagnetic compatibility: D0: IN1 OUT1
Electromagnetic compatibility: D1: IN2 OUT2
Electromagnetic compatibility: D2: IN3 OUT3
Electromagnetic compatibility: D3: IN4 -
Parameter bits (programmable via AS-i): function
Electromagnetic compatibility: P0: Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
Electromagnetic compatibility: P1: Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings)
Electromagnetic compatibility: P2: Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
Ambient temperature: -25 ... 60 °C (-13 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Degree of protection: IP54 according to EN 60529
Connection: AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101 Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar
Mass: 260 g
Mounting: 2 clips with ∅ 8 mm drill hole
Cable length: 0.7 m (Inputs) , 1.5 m (X1, X2)
Note: The flat cable routing is designed for 100 actuation cycles

Parametry logistyczne

ECCN:
Kraj pochodzenia: ID
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m