Pepperl+Fuchs 324436

KCD2-SLD-Ex1.1245

Solenoid Driver

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

This isolated barrier is used for intrinsic safety applications. 1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 12 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC 61508pa. It supplies power to solenoids, LEDs and audible alarms located in a hazardous area. The device is controlled with a loop powered signal or a bus powered logic signal. The device is immune to the test pulses of various control systems. The device simulates a minimum load at the input. The minimum load can be activated and de-activated. The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver. A line fault is indicated by a red LED and output via the fault indication output or a switch contact.

Parametry techniczne

Signal type: Digital Output
Safety Integrity Level (SIL): SIL 3
Connection: terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered
Rated voltage: 19 ... 30 V DC loop powered
Input current: 75 mA at 24 V , 270 Ω load
Power dissipation: 1.3 W at 24 V , 270 Ω load
Connection side: control side
Connection: terminals 5+, 6-
Test pulse length: max. 2 ms from DO card
Signal level: loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC
Rated current: 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current: < 200 mA , 10 ms loop powered
Connection side: field side
Connection: terminals 1+, 2-
Internal resistor: 240 Ω
Current: typ. 45 mA
Voltage: typ. 12 V
Current limit: 50 mA
Open loop voltage: typ. 24.6 V
Load: nominal 0.05 ... 18 kΩ
Output II: fault signal
: Connection: terminals 7, 8 , non-intrinsically safe
: Contact loading: 30 V DC/ 0.5 A resistive load
: Mechanical life: 105 switching cycles
: Energized/De-energized delay: ≤ 20 ms / ≤ 20 ms
Line fault detection: signal at short-circuit RB < 25 Ω, lead breakage RB > 50 kΩ ; test current < 500 µA
Output/other circuits: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2012 , EN 61326-3-2:2008 For further information see system description.
Degree of protection: IEC 60529:2013
Protection against electrical shock: EN 61010-1:2010
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: EXA 17 ATEX 0002 X
Electromagnetic compatibility: Marking: II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Output I: Ex ia
Electromagnetic compatibility: Voltage: 26 V
Electromagnetic compatibility: Current: 110 mA
Electromagnetic compatibility: Power: 715 mW
Supply: Maximum safe voltage: 60 V (Attention! The rated voltage can be lower.)
Input: Maximum safe voltage: 60 V (Attention! The rated voltage can be lower.)
Collective error message: Maximum safe voltage: 60 V (Attention! The rated voltage can be lower.)
Galvanic isolation: Output I/other circuits: safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010
UL approval: E106378
Directive conformity: Control drawing: 116-0448 (cULus)
IECEx approval: IECEx certificate: IECEx EXA 17.0001X
IECEx approval: IECEx marking: Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m