Pepperl+Fuchs 302575

LB2002AR

Digital Output with Position Feedback

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

The digital output features 1 output with 2 feedback inputs. 1 digital output, 2 digital inputs, Output voltage 24 V, max. internal resistance 210 Ω, Installation in Zone 2 or safe area, Positive or negative logic selectablepa. The device can be used to switch solenoids, sounders, or indicators (without line fault detection) in the field. Furthermore, the device accepts digital input signals of NAMUR sensors or mechanical contacts from the field. Open and short-circuit line faults are detected. The inputs and the output are galvanically isolated from the bus and the power supply.

Parametry techniczne

Occupied slots: 1
Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Power dissipation: 1.3 W
Power consumption: 1.8 W
Connection: backplane bus
Interface: manufacturer-specific bus to standard com unit
Number of channels: 2
Sensor interface: Connection: NAMUR sensor
Sensor interface: Connection [2]: volt-free contact
Connection: channel I: 2+, 5-; channel II: 3+, 6-
Rated values: acc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis: 1.2 ... 2.1 mA / ± 0.2 mA
Voltage: 8.2 V
Internal resistor: 1 kΩ
Line fault detection: can be switched on/off for each channel via configuration tool
Sensor interface: Connection: mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Sensor interface: Short-circuit: < 360 Ω
Sensor interface: Open-circuit: < 0.35 mA
Minimum pulse duration: 1 ms
Number of channels: 1
Suitable field devices: Field device: Solenoid Valve
Suitable field devices: Field device [2]: audible alarm
Suitable field devices: Field device [3]: visual alarm
Connection: channel I: 1+, 4-
Open loop voltage: 24 V
Current limit: 50 mA
Internal resistor: 210 Ω
Line fault detection: can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms)
Suitable field devices: Short-circuit: < 200 Ω
Suitable field devices: Open-circuit: > 1.2 kΩ
Response time: 20 ms (depending on bus cycle time)
Watchdog: within 0.5 s the device goes in safe state, e.g. after loss of communication
LED indication: LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel
Coding: optional mechanical coding via front socket
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Electromagnetic compatibility: NE 21
Degree of protection: IEC 60529
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 when mounted on backplane
Connection: removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Mass: approx. 110 g
Dimensions: 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Input: Voltage: 14.1 V
Input: Current: 16 mA
Input: Power: 55 mW (linear characteristic)
Input: Internal capacitance: 1.65 nF
Input: Internal inductance: 0 mH
Output: Voltage: 27.83 V
Output: Current: 183 mA
Output: Power: 1270 mW
Output: Internal capacitance: 1.65 nF
Output: Internal inductance: 0 mH
Certificate: PF 08 CERT 1234 X
Output: Marking: II 3 G Ex nA [ic] IIB T4 Gc
Galvanic isolation: Input/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply, internal bus: safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
ATEX approval: PF 08 CERT 1234 X
UL approval: Control drawing: 116-0321A
IECEx approval: BVS 09.0037X
UL approval: Approved for: Ex nA [ic] IIC T4 Gc
EAC approval: Russia: RU C-IT.MIII06.B.00129
Marine approval: Lloyd Register: 15/20021
Marine approval: DNV GL Marine: TAA0000034
Marine approval: American Bureau of Shipping: T1450280/UN
Marine approval: Bureau Veritas Marine: 22449/B0 BV
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary information: EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: Deutschland
EAN: 4050143070046
Waga: 0,12 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m