Opis

The PROFINET gateway is the interface between the I/O modules on the backplane and the control system. Interface between the I/O modules and the PCS/PLC, Mounting in Zone 2, Class I/Div.2 or in the safe area, Non-volatile memory for configuration and parameter settings, Communication via PROFINETpa. HART communication is via PROFINET or HART I/P. In addition to the input/output data of the I/O modules, the HART auxiliary variables can also be accessed in the process image.

Parametry techniczne

Connection: backplane bus
Rated voltage: 12 V DC , only in connection with the power supplies LB9***
Nominal voltage: 12 V DC ,
Power dissipation: 3.65 W
Power consumption: 3.65 W
Fieldbus type: PROFINET
Connection type: RJ-45 , via front connector
Transfer rate: 10BASE-T, 100BASE-TX 100 MBit/s
Station connection: directly to PCS or PLC or via hubs or switches
Cable type: SFTP in accordance with ISO/IEC 11801 for Cat 5e or better
Bus length: max. 100 m Per link
Addressing: DHCP, via controller (DCP) or fixed IP address
Ethernet address: IP V4 address (preset: DHCP on, changeable via display)
Supported I/O modules: LB1x01*…LB1x03*, LB1x08*, LB1x09*, LB2x01*…LB2x17*, LB3x01*…LB3x06*, LB4x01*, LB4x02*, LB4x04*…LB4x06*, LB5x01*, LB5x02*, LB5x04*…LB5x06*, LB6x01*, LB6x05*, LB6x06*, LB6x08*, LB6x10*…LB6x17*
HART communication: via PROFINET and HART I/P
PROFINET conformance class: CC B
Connection: backplane bus
Ethernet/other circuits: basic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
RS 485 interface/other circuits: basic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
Insulation voltage: 1500 V AC acc. to IEEE 802.3u
Power supply, internal bus/other circuits: basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1
Degree of protection: IEC 60529
Fieldbus standard: IEEE 802.3
Environmental test: EN 60068-2-14
Shock resistance: EN 60068-2-27
Vibration resistance: EN 60068-2-6
Damaging gas: EN 60068-2-42
Relative humidity: EN 60068-2-56
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Storage temperature: -25 ... 85 °C (-13 ... 185 °F)
Relative humidity: 95 % non-condensing
Shock resistance: shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistance: frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gas: designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protection: IP20 (module) , mounted on backplane
Connection: via backplane
Mass: approx. 150 g
Dimensions: 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Certificate: DEMKO 16 ATEX 1780 X
Electromagnetic compatibility: Marking: II 3 G Ex nA IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 EN 60079-15:2010
ATEX approval: DEMKO 16 ATEX 1780 X
IECEx approval: IECEx UL 16.0141 X
Directive conformity: Approved for: Ex nA IIC T4 Gc
System information: The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.