Opis

This isolated barrier is used for intrinsic safety applications. 2-channel isolated barrier, 24 V DC supply (Power Rail), Input 2-wire SMART transmitters, Output 0/2 V .. 10 V, Terminals with test points, Up to SIL 2 acc. to IEC 61508pa. The device supplies 2-wire SMART transmitters in a hazardous area. It transfers the analog input signal to the safe area as an isolated voltage value. Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally. If the HART communication resistance in the loop is too low, the internal resistance of 250 Ω between terminals 8, 9 and 11, 12 can be used. Test sockets for the connection of HART communicators are integrated into the terminals of the device.

Parametry techniczne

Signal type: Analog input
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 20 ... 35 V DC
Ripple: within the supply tolerance
Power dissipation: 1.8 W
Power consumption: max. 2.7 W
Connection side: field side
Connection: terminals 1+, 3-; 4+, 6-
Input signal: 0/4 ... 20 mA
Available voltage: ≥ 16 V at 20 mA, terminals 1+, 3
Connection side: control side
Connection: terminals 7-, 8+; 10-, 11+
Load: output resistance: 500 Ω
Output signal: 0/2 ... 10 V
Ripple: max. 25 mV
Deviation: at 20 °C (68 °F), 0/2 ... 10 V ≤ 10 mV incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
: Influence of ambient temperature: ≤ 20 ppm/K
Frequency range: field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Rise time: 20 µs
Settling time: 200 µs
De-energized delay: 20 µs
Output/power supply: functional insulation, rated insulation voltage 50 V AC
Output/Output: functional insulation, rated insulation voltage 50 V AC
Display elements: LED
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2011
Degree of protection: IEC 60529:2001
Protection against electrical shock: UL 61010-1:2012
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BAS 99 ATEX 7025 X
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Input: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Electromagnetic compatibility: Voltage: 25.2 V
Electromagnetic compatibility: Current: 93 mA
Electromagnetic compatibility: Power: 0.586 W
Supply: Maximum safe voltage: 250 V (Attention! The rated voltage can be lower.)
Certificate: TÜV 99 ATEX 1499 X
Supply: Marking: II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Input/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
UL approval: Control drawing: 116-0428 (cULus)
IECEx approval: IECEx BAS 04.0015X IECEx CML 15.0055X
UL approval: Approved for: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: Singapur
EAN: 4050143067213
Waga: 0,17 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m