Opis

This isolated barrier is used for intrinsic safety applications. 2-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 40 mA at 12 V DC, 55 mA current limit, Contact or logic control input, Entity parameter Io/Isc = 110 mA, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508 (bus powered), Up to SIL 3 acc. to IEC 61508 (loop powered)pa. It supplies power to solenoids, LEDs, and audible alarms, located in a hazardous area. It is controlled with a loop-powered control signal, switch contact, transistor, or logic signal. At full load, 12 V at 40 mA (with 55 mA current limit) is available for the hazardous area application. An alternative low current output is available for driving a single LED without installing an external current limiting resistor. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. This device mounts on a HiD Termination Board.

Parametry techniczne

Signal type: Digital Output
Safety Integrity Level (SIL): SIL 3
Connection: SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage: 20.4 ... 30 V DC loop powered 20.4 ... 30 V DC bus powered via Termination Board
Input current: 62 mA at 24 V, 300 Ω load (per channel)
Power dissipation: 1 W at 24 V, 300 Ω load (per channel)
Connection side: control side
Connection: SL1: 8a(+), 7a(-); 10a(+), 9a(-) bus powered SL1: 8b(+), 7b(-); 9b(+), 10b(-) loop powered
Control input: external switch (dry contact or open collector) non isolated or logic signal input fully floating
Signal level: 1-signal: 15...30 V DC (current limited at 3 mA) or contact close (internal 10 kΩ pull-up) 0-signal: 0...5 V DC or contact open
Power dissipation: 1 W at 24 V, 300 Ω load (per channel) for loop powered
Inrush current: 0.2 A , 15 ms loop powered
Connection side: field side
Connection: SL2: 5a(+), 5b(-), 7a(+); 1a(+), 1b(-), 3b(+)
Internal resistor: approx. 240 Ω
Current: ≤ 40 mA
Voltage: ≥ 12 V
Current limit: 55 mA
Open loop voltage: approx. 22.5 V
Load: nominal 0.1 ... 5 kΩ
Switching frequency: - bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz - loop powered: max. 10 Hz
Energized/De-energized delay: - bus powered: filter OFF: 1 ms, filter ON: 10 ms - loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Connection: SL1: 6b
Output type: open collector transistor (internal fault bus)
Fault current: 4 mA pulsing (20 ms ON, 200 ms OFF)
Fault level: lead short-circuit detection at < 25 Ω lead breakage detection at > 100 kΩ typical
Output/Output: safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Output/power supply, inputs, and collective error: safe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006 For further information see system description.
Degree of protection: IEC 60529:2001
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Relative humidity: 5 ... 90 %, non-condensing up to 35 °C (95 °F)
Degree of protection: IP20
Mass: approx. 140 g
Dimensions: 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mounting: on Termination Board
Coding: pin 1 and 4 trimmed For further information see system description.
EU-Type Examination Certificate: CESI 10 ATEX 036
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Output: Ex ia Ga, Ex ia Da, Ex ia Ma
Electromagnetic compatibility: Voltage: 26 V
Electromagnetic compatibility: Current: 110 mA
Electromagnetic compatibility: Power: 715 mW
Supply: Maximum safe voltage: 253 V AC (Attention! Um is no rated voltage.)
Certificate: PF 10 CERT 1729 X
Supply: Marking: II 3G Ex nA IIC T4 Gc
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 366-005CS-12B (cCSAus)
IECEx approval: IECEx CES 10.0013
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m