1-channel isolated barrier, 24 V DC supply (bus powered), Input for 2-wire SMART transmitters and current sources, Signal splitter (1 input and 2 outputs), Dual output 0/4 mA .. 20 mA or 0/1 V .. 5 V, Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources. It transfers the analog input signal to the safe area as two isolated output signals. Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data. The output is selected as a current source, current sink, or voltage source via switches. This device mounts on a HiC Termination Board.
Signal type: | Analog input |
Safety Integrity Level (SIL): | SIL 2 |
Connection: | SL1: 1a, 1b(-); 2a, 2b(+) |
Rated voltage: | 18 ... 30 V DC bus powered via Termination Board |
Ripple: | within the supply tolerance |
Power dissipation: | approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs |
Power consumption: | 2 W |
Connection side: | field side |
Connection: | SL2: 5a(+), 5b(-): sink SL2: 1a(+), 1b(-), 7a(-): source |
Input signal: | 0/4 ... 20 mA |
Voltage drop: | SL2: 1a(+), 1b(-), 7a(-): ≤ 6.1 V at 20 mA |
Short-circuit current: | SL2: 5a(+), 5b(-): 25 mA , wake up pulse: 36 mA, 20 ms (Honeywell DE) |
Input resistance: | SL2: 5a(+), 5b(-): max. 500 Ω (BRAIN) (250 Ω load) |
Available voltage: | SL2: 5a(+), 5b(-): ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA |
Connection side: | control side |
Connection: | SL1: 8a(+), 7a(-), channel 1: source and sink SL1: 10a(+), 9a(-), channel 2: source and sink |
Load: | channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V) |
Output signal: | 0/4 ... 20 mA or 0/1 ... 5 V |
Ripple: | max. 50 µA rms |
Deviation: | Iout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V |
: Influence of ambient temperature: | current output: 0.25 µA/K voltage output: 80 µV/K |
Frequency range: | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB) [DE 1 kHz (-3 dB)] |
Settling time: | 6 ms |
Rise time/fall time: | 2 ms |
Output/power supply: | functional insulation, rated insulation voltage 50 V AC |
Output/Output: | functional insulation, rated insulation voltage 50 V AC |
Display elements: | LED |
Control elements: | DIP-switch |
Configuration: | via DIP switches |
Labeling: | space for labeling at the front |
Electromagnetic compatibility: Directive 2014/30/EU: | EN 61326-1:2013 (industrial locations) |
Electromagnetic compatibility: | NE 21:2012 EN 61326-3-2:2008 |
Degree of protection: | IEC 60529:2001 |
Protection against electrical shock: | UL 61010-1:2012 |
Ambient temperature: | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection: | IP20 |
Mass: | approx. 100 g |
Dimensions: | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) |
Mounting: | on Termination Board |
Coding: | pin 2 and 3 trimmed For further information see system description. |
EU-type examination certificate: | BASEEFA 13 ATEX 0075 X |
Electromagnetic compatibility: Marking: | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Electromagnetic compatibility: Input: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
Equipment: | terminals 5a, 5b |
Supply: Voltage Uo: | 25.2 V |
Supply: Voltage Uq: | 28.2 V |
Supply: Current Io: | 93 mA |
Supply: Power Po: | 656 mW |
Supply: Internal capacitance Ci: | 12 nF |
Supply: Internal inductance Li: | 0 mH |
Equipment: | terminals 1a, 1b, 7a |
Supply: Voltage Ui: | 30 V |
Supply: Current Ii: | 115 mA |
Supply: Power Pi: | 700 mW |
Supply: Voltage Uo: | 5 V |
Supply: Current Io: | 6.8 mA |
Supply: Power Po: | 1.6 mW |
Output: Maximum safe voltage: | 250 V (Attention! The rated voltage can be lower.) |
Certificate: | BASEEFA 13 ATEX 0076 X |
Output: Marking: | II 3G Ex nA II T4 Gc [device in zone 2] |
Galvanic isolation: Input/Output: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Galvanic isolation: Input/power supply: | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity: Directive 2014/34/EU: | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
UL approval: Control drawing: | 116-0349 (cULus) |
IECEx approval: | IECEx BAS 13.0042X |
UL approval: Approved for: | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Note: | Both output loads must be connected to ensure complete and correct operation within the technical specification. |
Supplementary information: | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
ECCN: | |
Kraj pochodzenia: | Singapur |
EAN: | 4050143075867 |
Waga: | 0,14 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |