Pepperl+Fuchs 184258

KFD2-SL2-Ex2

Solenoid Driver

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

2-channel isolated barrier, 24 V DC supply (Power Rail), Output 45 mA at 11.7 V DC, Logic input, non-polarized, Line fault detection (LFD), Up to SIL 2 acc. to IEC 61508pa. This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area. It is controlled via logic signals. The inputs have two defined states: 1-Signal = 16 V DC ... 30 V DC, 0-Signal = 0 V DC ... 5 V DC. The current consumption of the input is about 3 mA. At full load, 11.7 V at 45 mA is available for the hazardous area application. If the field impedance is > 10 kΩ for lead breakage or < 50 Ω for short circuits a line fault is detected. A fault is signalized by LEDs and a separate collective error message output.

Parametry techniczne

Signal type: Digital Output
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 20 ... 30 V DC
Power consumption: max. 3.3 W at 45 mA output current
Connection side: control side
Connection: terminals 7, 8, 9
Input current: approx. 3 mA at 24 V DC
Signal level: 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC
Connection side: field side
Connection: channel 1: terminals 1+, 2-, 3 channel 2: terminals 4+, 5-, 6-
Internal resistor: 272 Ω
Current: ≤ 45 mA
Voltage: ≥ 11.7 V
Open loop voltage: min. 24 V
Output signal: These values are valid for the rated operating voltages from 20 ... 30 V DC.
Energized/De-energized delay: ≤ 20 ms / ≤ 20 ms
Line fault detection: signal at short-circuit RB < 50 Ω, lead breakage RB > 10 kΩ , test current < 650 µA
Input/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Power supply/Output: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Control elements: DIP-switch
Configuration: via DIP switches
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2006
Degree of protection: IEC 60529:2001
Protection against electrical shock: EN 61010-1:2010
Ambient temperature: -20 ... 50 °C (-4 ... 122 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: ZELM 00 ATEX 0024
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Output: Ex ia
Electromagnetic compatibility: Voltage: 28 V
Electromagnetic compatibility: Current: 110 mA
Electromagnetic compatibility: Power: 770 mW (linear characteristic)
Supply: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.)
Input: Maximum safe voltage: 60 V (Attention! The rated voltage can be lower.)
Collective error message: Maximum safe voltage: 40 V (Attention! The rated voltage can be lower.)
Certificate: TÜV 02 ATEX 1820 X
Collective error message: Marking: II 3G Ex nA IIC T4 Gc
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000
CSA approval: Control drawing: 116-0304
IECEx approval: IECEx certificate: IECEx TUN 04.0001
IECEx approval: IECEx marking: [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parametry logistyczne

ECCN:
Kraj pochodzenia: SG
EAN:
Waga: 0,00 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m