Pepperl+Fuchs 123524

KFD2-SCD2-EX1.LK

SMART Current Driver

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

1-channel isolated barrier, 24 V DC supply (Power Rail), Current output up to 650 Ω load, HART I/P and valve positioner, Line fault detection (LFD), Accuracy 0.1 %, Up to SIL 2 acc. to IEC 61508, Transfer direction: to the fieldpa. This isolated barrier is used for intrinsic safety applications. The device drives SMART I/P converters, electrical valves, and positioners in hazardous areas. Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally. Current transferred across the DC/DC converter is repeated at terminals 1 and 2. Terminals 2 and 3 are used when no short circuit detection is required. An open or short field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system. If the HART communication resistance in the loop is too low, the internal resistance can be used. Test sockets for the connection of HART communicators are integrated into the terminals of the device. A fault is signalized by LEDs and a separate collective error message output.

Parametry techniczne

Signal type: Analog output
Safety Integrity Level (SIL): SIL 2
Connection: Power Rail or terminals 14+, 15-
Rated voltage: 19 ... 30 V DC
Ripple: ≤ 10 %
Rated current: ≤ 30 mA at 24 V
Power dissipation: ≤ 600 mW at 20 mA and 500 Ω load
Power consumption: ≤ 700 mW
Connection side: control side
Connection: terminals 7-, 8+, (9+)
Input signal: 4 ... 20 mA , limited to approx. 30 mA
Input voltage: open loop voltage of the control system ≤ 30 V
Voltage drop: approx. 6 V at 20 mA
Input resistance: field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 1 and 2
Connection side: field side
Connection: terminals 1+, 2- terminals 3+, 2- (no short circuit detection)
Voltage: ≥ 13 V at 20 mA
Current: 4 ... 20 mA
Load: 100 ... 650 Ω , for terminals 1, 2 0 ... 550 Ω , for terminals 2, 3
Ripple: 20 mV rms
Line fault detection: breakage, load > 100 kΩ, short-circuit, load < 70 Ω
Output type: open collector transistor (internal fault bus)
Accuracy: 0.1 %
Deviation: at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis
: Influence of ambient temperature: < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Frequency range: field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time: 10 to 90 % ≤ 10 ms
Linearity: < ± 0.1 % of full-scale value
Input/Output: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply: basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply: reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Display elements: LEDs
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Electromagnetic compatibility: NE 21:2017 EN 61326-3-2:2018
Degree of protection: IEC 60529
Protection against electrical shock: UL 61010-1:2012
Ambient temperature: -40 ... 70 °C (-40 ... 158 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 115 g
Dimensions: 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificate: BAS 00 ATEX 7240 X
Electromagnetic compatibility: Marking: II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Electromagnetic compatibility: Output: Ex ia, Ex iaD
Electromagnetic compatibility: Voltage: 25.2 V
Electromagnetic compatibility: Current: 93 mA
Electromagnetic compatibility: Power: 585.3 mW
Electromagnetic compatibility: Internal capacitance: 1.05 nF
Electromagnetic compatibility: Internal inductance: 0
Supply: Maximum safe voltage: 250 V rms (Attention! The rated voltage can be lower.)
Input: Maximum safe voltage: 250 V rms (Attention! The rated voltage can be lower.)
Certificate: TÜV 99 ATEX 1499 X
Input: Marking: II 3G Ex nA II T4
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Galvanic isolation: Output/power supply: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2018 , EN 60079-11:2012 , EN 60079-15:2005
UL approval: E106378
Directive conformity: Control drawing: 116-0345 (cULus)
IECEx approval: IECEx certificate: IECEx BAS 04.0014X
IECEx approval: IECEx marking: [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Optional accessories: - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)

Parametry logistyczne

ECCN:
Kraj pochodzenia: Singapur
EAN: 4050143059898
Waga: 0,15 kg
Długość: 0,00 m
Szerokość: 0,00 m