High precision across the entire temperature measurement range. Particularly good response dynamics and very short power-on delay time. Robust stainless steel housing with very high pressure rating. With AS-i interface. High protection rating for the requirements of harsh industrial environments

Parametry techniczne

Number of inputs and outputs: Number of analogue outputs: 1
Measuring range: -10...150 °C 14...302 °F
-10...150 °C: 14...302 °F
Process connection: threaded connection G 1/2 external thread
Installation length EL [mm]: 87.5
Special feature: Gold-plated contacts
Measuring element: 1 x Pt 1000; (to DIN EN 60751, class A)
Media: liquids and gases
Medium temperature: < 150; (< 40 min) °C < 302; (< 40 min) °F
< 150; (< 40 min) °C: < 302; (< 40 min) °F
Pressure rating [bar]: 300
Note on pressure rating: sensor When mounted in adapters the specifications of the adapter data sheet apply.
Minimum installation depth [mm]: 15
Operating voltage [V]: 18...31.6 DC
Current consumption [mA]: < 25
Protection class: III
Reverse polarity protection: yes
Number of inputs and outputs: Number of analogue outputs: 1
Total number of outputs: 1
Output signal: analogue signal
Electrical design: AS-i
Number of analogue outputs: 1
Overload protection: yes
Probe length L [mm]: 87.5
Measuring range: -10...150 °C 14...302 °F
-10...150 °C: 14...302 °F
Resolution of analogue output [K]: 0.05
Precision analogue output [K]: ± 0,1 (60°C / 140°F ) / ± 0,3 (0...140°C / 32...284°F)
Temperature coefficient [% of the span / 10 K]: < ± 0,1; (in case of deviation from the reference condition 25 ± 5 °C)
Dynamic response T05 / T09 [s]: 1 / 3; (to DIN EN 60751)
Ambient temperature [°C]: -25...70
Storage temperature [°C]: -40...100
Protection: IP 68; IP 69K
EMC: DIN EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m DIN EN 61000-4-4 Burst 2 kV DIN EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V
DIN EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
DIN EN 61000-4-4 Burst: 2 kV
DIN EN 61000-4-5 Surge: 0,5/1 kV
EN 61000-4-6 HF conducted: 10 V
Shock resistance: DIN IEC 68-2-27 50 g (11 ms)
DIN IEC 68-2-27: 50 g (11 ms)
Vibration resistance: DIN EN 60068-2-6 20 g (10...2000 Hz)
DIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]: 348
AS-i version: 2.11
AS-i I/O configuration [hex]: 7
AS-i ID code [hex]: 3.C
Weight [g]: 258.5
Dimensions [mm]: Ø 30 / L = 190.5
Materials: stainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); stainless steel (1.4305 / 303); PA
Materials (wetted parts): stainless steel (1.4404 / 316L)
Tightening torque [Nm]: 30...50
Process connection: threaded connection G 1/2 external thread
Installation length EL [mm]: 87.5
Display: operation 1 x LED, green failure 1 x LED, red
operation: 1 x LED, green
failure: 1 x LED, red
Remarks: The values for accuracy apply to flowing water. referring to UL: for use on a low voltage circuit with overcurrent protection in accordance with UL873 tab. 28.1 or Imax = 100/Ub (Ub = voltage of the circuit)
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,26 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m