Flow monitor. SID10ADBFKOW/LS-100-IRF
Reliable monitoring of liquids and gases in pipes. Variable process connection using adapters. Easy setting of the switch points for quick set-up. Robust stainless steel housing for use in harsh industrial environments. LED bar graph for indication of switch point and flow
| Number of inputs and outputs: | Number of digital outputs: 1 |
| Process connection: | G 1/4 external thread |
| Media: | Liquids; Gases |
| Medium temperature [°C]: | -25...80 |
| Pressure rating [bar]: | 300 |
| Medium temperature [°C]: | -25...80 |
| Medium temperature [°C]: | -25...80 |
| Operating voltage tolerance [%]: | -5...10 |
| Operating voltage [V]: | 85...265 AC |
| Nominal voltage AC [V]: | < 240 |
| Protection class: | II |
| Reverse polarity protection: | no |
| Power-on delay time [s]: | 10 |
| Number of inputs and outputs: | Number of digital outputs: 1 |
| Total number of outputs: | 1 |
| Output signal: | switching signal |
| Electrical design: | relay |
| Number of digital outputs: | 1 |
| Output function: | normally open / normally closed; (parameterisable) |
| Contact rating: | 3 A (250 V AC / 30 V DC); (number of switching cycles: 20 million mechanically; switching cycles at 3 A load: 100,000 electrical; type of switch-off: normally open) |
| Short-circuit proof: | no |
| Overload protection: | no |
| Setting range [cm/s]: | 3...300 |
| Greatest sensitivity [cm/s]: | 3...100 |
| Setting range [cm/s]: | 200...3000 |
| Greatest sensitivity [cm/s]: | 200...800 |
| Repeatability [cm/s]: | 1...5 |
| Note on repeatability: | for water 5...100 cm/s; 25 °C Factory setting |
| Temperature drift [cm/s x 1/K]: | 0.1; (for water 5...100 cm/s; 10...70 °C) |
| Temperature gradient [K/min]: | 300 |
| Switch point accuracy [cm/s]: | ± 2...± 10; (for water 5...100 cm/s; 25 °C; Factory setting) |
| Hysteresis [cm/s]: | 2...5; (for water 5...100 cm/s; 25 °C; Factory setting) |
| Response time [s]: | 1...10 |
| Response time [s]: | 1...10 |
| Response time [s]: | 1...10 |
| Adjustment of the switch point: | pushbutton |
| Ambient temperature [°C]: | -25...80 |
| Storage temperature [°C]: | -25...100 |
| Protection: | IP 67 |
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V |
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated: | 10 V/m |
| EN 61000-4-4 Burst: | 2 kV |
| EN 61000-4-6 HF conducted: | 10 V |
| Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
| DIN IEC 68-2-27: | 50 g (11 ms) |
| Vibration resistance: | DIN EN 60068-2-6 20 g (55...2000 Hz) |
| DIN EN 60068-2-6: | 20 g (55...2000 Hz) |
| MTTF [years]: | 220.97 |
| Weight [g]: | 304 |
| Materials: | stainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); PC; PBT-GF20; EPDM/X |
| Materials (wetted parts): | stainless steel (1.4404 / 316L); O-ring: FKM 80 Shore A |
| Tightening torque [Nm]: | 25 |
| Process connection: | G 1/4 external thread |
| Display: | function 10 x LED, three-colour |
| function: | 10 x LED, three-colour |
| Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting |
| Remarks: | Recommendation Check the safe functioning of the unit after a short circuit. |
| Notes: | discontinued article |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: 1 x 1/2" |
| ECCN: | |
| Kraj pochodzenia: | DEUTSCHLAND |
| EAN: | |
| Waga: | 0,29 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |