SBG257
Flow meter with integrated backflow prevention and display. SBG54IF0FRKG
Precise detection of flow and medium temperature. Suitable for water, coolants, oil and glycol solutions thanks to integrated measurement graphs. Reliable backflow prevention with very fast response time. With switching output, analogue output or frequency output and IO-Link. Clearly visible LED display with red/green colour change
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Process connection: | threaded connection G 1 1/4 |
Measuring range [°C]: | -10...100 |
Special feature: | Gold-plated contacts |
Application: | for industrial applications |
Media: | water; glycol solutions; coolants; oil |
Note on media: | oil 1 with viscosity: 10 mm²/s (40 °C) oil 2 with viscosity: 46 mm²/s (40 °C) |
Medium temperature [°C]: | -10...100 |
Pressure rating [bar]: | 25 |
MAWP (for applications according to CRN) [bar]: | 25 |
Operating voltage [V]: | 18...30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA]: | < 50 |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | < 3 |
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; frequency signal; IO-Link; (configurable) |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 150; (per output 2 x 200 (...60 °C); 2 x 250 (...40 °C)) |
Switching cycles (mechanical): | 10 million |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20 |
Max. load [Ω]: | 500 |
Short-circuit protection: | yes |
Overload protection: | yes |
Frequency of the output [Hz]: | 0...10000 |
Measuring range: | 4...200 l/min 0.24...12 m³/h |
4...200 l/min: | 0.24...12 m³/h |
Display range: | 0...240 l/min 0...14.4 m³/h |
0...240 l/min: | 0...14.4 m³/h |
Resolution: | 1 l/min 0.05 m³/h |
1 l/min: | 0.05 m³/h |
Set point SP: | 2...200 l/min 0.1...12 m³/h |
2...200 l/min: | 0.1...12 m³/h |
Reset point rP: | 0...198 l/min 0...11.9 m³/h |
0...198 l/min: | 0...11.9 m³/h |
Frequency end point, FEP: | 13...200 l/min 0.8...12 m³/h |
13...200 l/min: | 0.8...12 m³/h |
In steps of: | 1 l/min 0.05 m³/h |
1 l/min: | 0.05 m³/h |
Frequency at the end point FRP [Hz]: | 10...10000 |
Measuring dynamics: | 1:50 |
Measuring range [°C]: | -10...100 |
Display range [°C]: | -32...122 |
Resolution [°C]: | 1 |
Set point SP [°C]: | -9...100 |
Reset point rP [°C]: | -10...99 |
In steps of [°C]: | 1 |
Frequency start point, FSP [°C]: | -10...78 |
Frequency end point, FEP [°C]: | 12...100 |
Frequency at the end point FRP [Hz]: | 10...10000 |
Accuracy (in the measuring range): | ± (4 % MW + 1 % MEW); (Q > 1 l/min; medium and operating temperature: +22 °C ± 4K) |
Repeatability: | ± 1 % MEW |
Temperature drift: | 0,029 °C / K |
Accuracy [K]: | 3 K (25°C; Q > 1 l/min) |
Response time [s]: | 0.01 |
Damping for the switching output dAP [s]: | 0...5 |
Damping for the analogue output dAA [s]: | 0...5 |
Dynamic response T05 / T09 [s]: | T09 = 120 (Q > 1 l/min) |
Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 CDV |
IO-Link device ID: | 564 d / 0234 h |
Profiles: | Smart Sensor: Process Data Variable; Device Identification |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 2 |
Process data binary: | 2 |
Min. process cycle time [ms]: | 5 |
Ambient temperature [°C]: | 0...60 |
Note on ambient temperature: | medium temperature < 80 °C medium temperature < 100 °C: 0...40 °C |
Storage temperature [°C]: | -15...80 |
Protection: | IP 65; IP 67 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 |
Shock resistance: | DIN EN 60068-2-27 20 g (11 ms) |
DIN EN 60068-2-27: | 20 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 5 g (10...2000 Hz) |
DIN EN 60068-2-6: | 5 g (10...2000 Hz) |
MTTF [years]: | 145 |
UL approval: | UL Approval no. I007 |
UL Approval no.: | I007 |
Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g]: | 1977.5 |
Materials: | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated |
Materials (wetted parts): | stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; PP-GF30; O-ring: FKM |
Process connection: | threaded connection G 1 1/4 |
Display: | Display unit 3 x LED, green switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit programming alphanumeric display, 4-digit |
Display unit: | 3 x LED, green |
switching status: | 2 x LED, yellow |
measured values: | alphanumeric display, red/green 4-digit |
programming: | alphanumeric display, 4-digit |
Remarks: | Recommendation: use a 200-micron filter. All data refer to water (20 °C). MW = measured value MEW = Final value of the measuring range |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 1,98 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |