Ifm SBG232

Flow meter with integrated backflow prevention and display. SBG12IF0FRKG

Na prośbę. Prześlij nam wiadomość e-mail z zapytaniem o cenę i dostępność.
"ucnguBrctvdgcxgt0eqo"

Opis

Precise detection of flow and medium temperature. Suitable for water, coolants, oil and glycol solutions thanks to integrated measurement graphs. Reliable backflow prevention with very fast response time. With switching output, analogue output and frequency output. Clearly visible LED display with red/green colour change

Parametry techniczne

Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Process connection: threaded connection G 1/2
Measuring range [°C]: -10...100
Special feature: Gold-plated contacts
Application: for industrial applications
Media: water; glycol solutions; coolants; oil
Note on media: oil 1 with viscosity: 10 mm²/s (40 °C) oil 2 with viscosity: 46 mm²/s (40 °C)
Medium temperature [°C]: -10...100
Pressure rating [bar]: 40
MAWP (for applications according to CRN) [bar]: 40
Operating voltage [V]: 18...30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: < 50
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: < 3
Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Total number of outputs: 2
Output signal: switching signal; analogue signal; frequency signal; IO-Link; (configurable)
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 150; (per output 2 x 200 (...60 °C); 2 x 250 (...40 °C))
Switching cycles (mechanical): 10 million
Number of analogue outputs: 1
Analogue current output [mA]: 4...20
Max. load [Ω]: 500
Short-circuit protection: yes
Overload protection: yes
Frequency of the output [Hz]: 0...10000
Measuring range: 0.3...15 l/min 0.018...0.9 m³/h
0.3...15 l/min: 0.018...0.9 m³/h
Display range: 0...18 l/min 0...1.08 m³/h
0...18 l/min: 0...1.08 m³/h
Resolution: 0.05 l/min 0.005 m³/h
0.05 l/min: 0.005 m³/h
Set point SP: 0.1...15 l/min 0.005...0.9 m³/h
0.1...15 l/min: 0.005...0.9 m³/h
Reset point rP: 0...14.9 l/min 0...0.895 m³/h
0...14.9 l/min: 0...0.895 m³/h
Frequency end point, FEP: 1...15 l/min 0.06...0.9 m³/h
1...15 l/min: 0.06...0.9 m³/h
In steps of: 0.05 l/min 0.005 m³/h
0.05 l/min: 0.005 m³/h
Frequency at the end point FRP [Hz]: 10...10000
Measuring dynamics: 1:50
Measuring range [°C]: -10...100
Display range [°C]: -32...122
Resolution [°C]: 1
Set point SP [°C]: -9...100
Reset point rP [°C]: -10...99
In steps of [°C]: 1
Frequency start point, FSP [°C]: -10...78
Frequency end point, FEP [°C]: 12...100
Frequency at the end point FRP [Hz]: 10...10000
Accuracy (in the measuring range): ± (4 % MW + 1 % MEW); (Q > 0,3 l/min; medium and operating temperature: +22 °C ± 4K)
Repeatability: ± 1 % MEW
Temperature drift: 0,029 °C / K
Accuracy [K]: 3 K (25°C; Q > 1 l/min)
Response time [s]: 0.01
Damping for the switching output dAP [s]: 0...5
Damping for the analogue output dAA [s]: 0...5
Dynamic response T05 / T09 [s]: T09 = 120 (Q > 1 l/min)
Parameter setting options: hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; damping for the switching output / analogue output; display can be rotated and switched off; standard unit of measurement; process value colour
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
SDCI standard: IEC 61131-9 CDV
IO-Link device ID: 560 d / 0230 h
Profiles: Smart Sensor: Process Data Variable; Device Identification
SIO mode: yes
Required master port type: A
Process data analogue: 2
Process data binary: 2
Min. process cycle time [ms]: 5
Ambient temperature [°C]: 0...60
Note on ambient temperature: medium temperature < 80 °C medium temperature < 100 °C: 0...40 °C
Storage temperature [°C]: -15...80
Protection: IP 65; IP 67
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3
Shock resistance: DIN EN 60068-2-27 20 g (11 ms)
DIN EN 60068-2-27: 20 g (11 ms)
Vibration resistance: DIN EN 60068-2-6 5 g (10...2000 Hz)
DIN EN 60068-2-6: 5 g (10...2000 Hz)
MTTF [years]: 145
UL approval: UL Approval no. I005
UL Approval no.: I005
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 750
Materials: stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC; brass chemically nickel-plated
Materials (wetted parts): stainless steel (1.4401 / 316); stainless steel (1.4404 / 316L); brass (2.0371); brass chemically nickel-plated; PPS; O-ring: FKM
Process connection: threaded connection G 1/2
Display: Display unit 3 x LED, green switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit programming alphanumeric display, 4-digit
Display unit: 3 x LED, green
switching status: 2 x LED, yellow
measured values: alphanumeric display, red/green 4-digit
programming: alphanumeric display, 4-digit
Remarks: Recommendation: use a 200-micron filter. All data refer to water (20 °C). MW = measured value MEW = Final value of the measuring range
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Parametry logistyczne

ECCN:
Kraj pochodzenia: DE
EAN:
Waga: 0,75 kg
Długość: 0,00 m
Szerokość: 0,00 m
Wysokość: 0,00 m