SA5040
Flow sensor. SAD10XDBFRKG/US-100
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Process connection: | threaded connection M18 x 1,5 internal thread |
Special feature: | Gold-plated contacts |
Media: | water; glycol solutions; air; oils |
Note on media: | low-viscosity oils with viscosity: ≤ 40 mm²/s (40 °C) high-viscosity oils with viscosity: > 40 mm²/s (40 °C) |
Medium temperature [°C]: | -20...90 |
Pressure rating [bar]: | 100 |
Operating voltage [V]: | 18...30 DC |
Current consumption [mA]: | < 100 |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 10 |
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; frequency signal; IO-Link; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 250 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20; (scalable) |
Max. load [Ω]: | 350 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Frequency of the output [Hz]: | 0...1000 |
Probe length L [mm]: | 45 |
Operating mode: | relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended) |
Note on factory setting: | Operating mode: relative |
Setting range [m/s]: | 0.04...6 |
Greatest sensitivity [m/s]: | 0.04...3 |
Setting range [m/s]: | 0...200 |
Greatest sensitivity [m/s]: | 2...100 |
Measuring range [°C]: | -20...90 |
Resolution [°C]: | 0.2 |
Temperature drift [cm/s x 1/K]: | 0,003 m/s x 1/K (< 20 °C; > 70 °C) |
Temperature gradient [K/min]: | 100 |
Accuracy: | ± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions :; water: 20...70 °C; inlet length: 1.5 m; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.) |
Repeatability: | 0,05 m/s; (water; flow velocity: 0,05...3 m/s) |
Temperature drift: | ± 0,005 K/°C |
Accuracy [K]: | ± 0,3 / ± 1; (water; flow velocity: 0,3...3 m/s / air; flow velocity: > 10 m/s) |
Response time [s]: | 0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09) |
Dynamic response T05 / T09 [s]: | 1,5 (T09); (water; flow velocity: 0,3...3 m/s) |
Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 533 d / 00 02 15 h (REL) |
Profiles: | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 2 |
Process data binary: | 2 |
Min. process cycle time [ms]: | 3 |
Ambient temperature [°C]: | -40...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 65; IP 67 |
EMC: | DIN EN 60947-5-9 |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
DIN EN 60068-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 143 |
UL approval: | UL Approval no. I003 File number UL E174189 |
UL Approval no.: | I003 |
File number UL: | E174189 |
Weight [g]: | 311.5 |
Materials: | stainless steel (1.4404 / 316L); stainless steel (1.4310 / 301); PBT-GF20; PBT-GF30 |
Materials (wetted parts): | stainless steel (1.4404 / 316L); Gasket: EPDM |
Process connection: | threaded connection M18 x 1,5 internal thread |
Display: | Display unit 6 x LED, green (%, m/s, l/min, m³/h, °C, 10³) switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit |
Display unit: | 6 x LED, green (%, m/s, l/min, m³/h, °C, 10³) |
switching status: | 2 x LED, yellow |
measured values: | alphanumeric display, red/green 4-digit |
Remarks: | MW = measured value MEW = Final value of the measuring range 540 d / 00 02 1ch (LIQU) 547 d / 00 02 23 h (GAS) |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 0,31 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |