SA3010
Flow monitor. SAD18BBDFRKG/W/US-100-IPF
Reliable monitoring of water in pipes. Two switching outputs, one of them programmable as analogue output. Easy setting of the switch points for quick set-up. Robust housing for use in harsh industrial environments. LED display for indication of the measured value
| Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Special feature: | Gold-plated contacts |
| Installation: | T-pieces; ((DIN 2353): QL 18-18-18 (NW 15 mm) / QL 22-18-22 (NW 19 mm) / QL 28-18-28 (NW 24 mm)) |
| Media: | water |
| Medium temperature [°C]: | 0...80 |
| Pressure rating [bar]: | 30 |
| Operating voltage [V]: | 20...28 DC |
| Current consumption [mA]: | < 80 |
| Protection class: | III |
| Reverse polarity protection: | yes |
| Power-on delay time [s]: | 10 |
| Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Total number of outputs: | 2 |
| Output signal: | switching signal; analogue signal; (configurable) |
| Electrical design: | PNP/NPN |
| Number of digital outputs: | 2 |
| Output function: | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V]: | 2 |
| Permanent current rating of switching output DC [mA]: | 250; (per output) |
| Number of analogue outputs: | 1 |
| Analogue current output [mA]: | 4...20; (scalable) |
| Max. load [Ω]: | 500 |
| Analogue voltage output [V]: | 0...10; (scalable) |
| Min. load resistance [Ω]: | 2000 |
| Short-circuit protection: | yes |
| Type of short-circuit protection: | pulsed |
| Overload protection: | yes |
| Measuring range [l/min]: | 0...10 |
| Display range [l/min]: | 0...12 |
| Set point SP [l/min]: | 0.1...12 |
| Reset point rP [l/min]: | 0...11.9 |
| Analogue start point ASP [l/min]: | 0...8 |
| Analogue end point AEP [l/min]: | 4...12 |
| In steps of [l/min]: | 0.1 |
| Repeatability [% of the measured value]: | 3 (Q < 30%) / 7 (Q < 100%) |
| Temperature gradient [K/min]: | 200 |
| Accuracy (in the measuring range): | ± 10 |
| Response time [s]: | 5; (10%...90%) |
| Delay time programmable dS, dr [s]: | 0...50 |
| Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; current/voltage output; inside pipe diameter; start-up delay; adaptation of displayed values; display can be rotated and switched off; Display unit |
| Ambient temperature [°C]: | -20...60 |
| Protection: | IP 67 |
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V |
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated: | 10 V/m |
| EN 61000-4-4 Burst: | 2 kV |
| EN 61000-4-6 HF conducted: | 10 V |
| MTTF [years]: | 184 |
| Weight [g]: | 330.5 |
| Materials: | stainless steel (1.4404 / 316L); PBT; PC; PA; EPDM/X; FKM |
| Materials (wetted parts): | stainless steel (1.4404 / 316L); O-ring: FKM 70 Shore A |
| Display: | switching status 2 x LED, red measured values 7-segment LED display programming 7-segment LED display |
| switching status: | 2 x LED, red |
| measured values: | 7-segment LED display |
| programming: | 7-segment LED display |
| Display unit: | l/min; gpm; l/h; gph; m³/h |
| Remarks: | NW = nominal diameter |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: 1 x M12; Contacts: gold-plated |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,33 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |