PV2123
Pressure switch with IO-Link. PV-060-SEG14-UFRVG/US/ /
Output signal: | switching signal; IO-Link; (configurable) |
Measuring range [bar]: | 0...60 |
Process connection: | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Measuring element: | metallic thin film cell |
Application: | for industrial applications |
Media: | liquids and gases |
Medium temperature [°C]: | -40...90 |
Min. bursting pressure [bar]: | 900 |
Pressure rating [bar]: | 150 |
Note on pressure rating: | static |
Vacuum resistance [mbar]: | -1000 |
Type of pressure: | relative pressure |
Operating voltage [V]: | 18...30 DC |
Current consumption [mA]: | < 15 |
Min. insulation resistance [MΩ]: | 100; (500 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | < 0.3 |
Number of inputs and outputs: | Number of digital outputs: 2 |
Total number of outputs: | 2 |
Output signal: | switching signal; IO-Link; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 100 |
Switching frequency DC [Hz]: | < 170 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range [bar]: | 0...60 |
Set point SP [bar]: | 0.6...60 |
Reset point rP [bar]: | 0.3...59.7 |
In steps of [bar]: | 0.02 |
Factory setting: | SP1 = 2.0 bar rP1 = 1.5 bar ou1 = Hno; SP2 = 2.0 bar rP2 = 1.5 bar ou2 = Hno; dS1/dS2 = 0 ms dr1/dr2 = 0 ms coF = 0 % P-n = PnP dAP= 60 ms |
SP1 = 2.0 bar: | rP1 = 1.5 bar |
SP2 = 2.0 bar: | rP2 = 1.5 bar |
dS1/dS2 = 0 ms: | dr1/dr2 = 0 ms |
coF = 0 %: | P-n = PnP |
Switch point accuracy [% of the span]: | < ± 0,5 (nach DIN EN 61298-2) |
Repeatability [% of the span]: | < ± 0,05; (with temperature fluctuations < 10 K) |
Characteristics deviation [% of the span]: | < ± 0,5 (nach DIN EN 61298-2); (incl. drift when overtightened, zero point and span error, non-linearity, hysteresis) |
Linearity deviation [% of the span]: | < ± 0,1 (BFSL) / < ± 0,2 (LS) |
Hysteresis deviation [% of the span]: | < ± 0,2 |
Long-term stability [% of the span]: | < ± 0,1; (per 6 months) |
Temperature coefficient zero point [% of the span / 10 K]: | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |
Temperature coefficient span [% of the span / 10 K]: | < 0,1 (-25...90 °C) / < 0,2 (-40...-25 °C) |
Response time [ms]: | < 3 |
Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; switch-on/switch-off delay; Damping |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 856 d / 00 03 58 h |
Profiles: | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 2 |
Process data binary: | 2 |
Min. process cycle time [ms]: | 5 |
Ambient temperature [°C]: | -40...90 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 67; IP 69K |
EMC: | DIN EN 61326-1 |
Shock resistance: | DIN EN 60068-2-27 500 g (1 ms) |
DIN EN 60068-2-27: | 500 g (1 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 668 |
UL approval: | UL Approval no. J015 |
UL Approval no.: | J015 |
Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g]: | 60.5 |
Materials: | 1.4542 (17-4 PH / 630); stainless steel (1.4404 / 316L); PEI |
Materials (wetted parts): | 1.4542 (17-4 PH / 630) |
Min. pressure cycles: | 60 million; (at 1.2 times nominal pressure) |
Tightening torque [Nm]: | 25...35; (recommended tightening torque; depends on lubrication, seal and pressure rating) |
Process connection: | threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal thread:M5 |
Process connection sealing: | FKM (to DIN 3869) |
Restrictor element integrated: | no (can be retrofitted) |
Remarks: | BFSL = Best Fit Straight Line LS = limit value setting |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12 |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 0,06 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |