PN7009
Pressure sensor with display. PN-1-1BRBR14-QFRKG/US/ /
Two programmable switching outputs. With long-term stability thanks to high overload protection. Lifespan of more than 100 million pressure cycles. Clearly visible 4-digit LED display. Country-specific pressure units selectable
| Output signal: | switching signal; IO-Link; (configurable) |
| Measuring range: | -1...1 bar -1000...1000 mbar |
| -1...1 bar: | -1000...1000 mbar |
| Process connection: | threaded connection G 1/4 internal thread |
| Special feature: | Gold-plated contacts |
| Application: | for industrial applications |
| Media: | liquids and gases |
| Medium temperature [°C]: | -25...80 |
| Min. bursting pressure [mbar]: | 50000 |
| Pressure rating [mbar]: | 20000 |
| Type of pressure: | relative pressure |
| Operating voltage [V]: | 18...36 DC; (according to EN 50178 SELV/PELV) |
| Current consumption [mA]: | < 35 |
| Min. insulation resistance [MΩ]: | 100; (500 V DC) |
| Protection class: | III |
| Reverse polarity protection: | yes |
| Overvoltage protection: | yes; (< 40 V) |
| Power-on delay time [s]: | 0.3 |
| Integrated watchdog: | yes |
| Number of inputs and outputs: | Number of digital outputs: 2 |
| Total number of outputs: | 2 |
| Output signal: | switching signal; IO-Link; (configurable) |
| Electrical design: | PNP/NPN |
| Number of digital outputs: | 2 |
| Output function: | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V]: | 2 |
| Permanent current rating of switching output DC [mA]: | 250 |
| Switching frequency DC [Hz]: | < 170 |
| Short-circuit protection: | yes |
| Type of short-circuit protection: | pulsed |
| Measuring range: | -1...1 bar -1000...1000 mbar |
| -1...1 bar: | -1000...1000 mbar |
| Set point SP [mbar]: | -970...1000 |
| Reset point rP [mbar]: | -980...990 |
| In steps of [mbar]: | 10 |
| Factory setting: | SP1 = -500 mbar rP1 = -540 mbar SP2 = 500 mbar rP2 = 460 mbar |
| Switch point accuracy [% of the span]: | < ± 0,5 |
| Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span]: | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span]: | < ± 0,25 |
| Long-term stability [% of the span]: | < ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K]: | 0,2; (-20...80 °C) |
| Temperature coefficient span [% of the span / 10 K]: | 0,2; (-20...80 °C) |
| Delay time programmable dS, dr [s]: | 0; 0,2...50 |
| Parameter setting options: | hysteresis / window; normally open / normally closed; diagnostic function; switching logic; switch-on/switch-off delay; Damping; Display unit |
| Communication interface: | IO-Link |
| Transmission type: | COM2 (38,4 kBaud) |
| IO-Link revision: | 1.1 |
| SDCI standard: | IEC 61131-9 CDV |
| IO-Link device ID: | 314 d / 00 01 3A h |
| Profiles: | no profile |
| SIO mode: | yes |
| Required master port type: | A |
| Process data analogue: | 1 |
| Process data binary: | 2 |
| Min. process cycle time [ms]: | 2.3 |
| Ambient temperature [°C]: | -20...80 |
| Storage temperature [°C]: | -40...100 |
| Protection: | IP 65 |
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V |
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated: | 10 V/m |
| EN 61000-4-4 Burst: | 2 kV |
| EN 61000-4-5 Surge: | 0,5/1 kV |
| EN 61000-4-6 HF conducted: | 10 V |
| Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
| DIN IEC 68-2-27: | 50 g (11 ms) |
| Vibration resistance: | DIN IEC 68-2-6 20 g (10...2000 Hz) |
| DIN IEC 68-2-6: | 20 g (10...2000 Hz) |
| MTTF [years]: | 219 |
| Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight [g]: | 261 |
| Materials: | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
| Materials (wetted parts): | stainless steel (1.4305 / 303); ceramics; FKM |
| Min. pressure cycles: | 100 million |
| Process connection: | threaded connection G 1/4 internal thread |
| Restrictor element integrated: | no (can be retrofitted) |
| Display: | Display unit 4 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit |
| Display unit: | 4 x LED, green |
| switching status: | 2 x LED, yellow |
| function display: | alphanumeric display, 4-digit |
| measured values: | alphanumeric display, 4-digit |
| Notes: | discontinued article |
| Pack quantity: | 1 pcs. |
| ECCN: | |
| Kraj pochodzenia: | DE |
| EAN: | |
| Waga: | 0,26 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |