PIM694
Pressure sensor with diagnostic function for pumps. PIM010-REA01-KFPKG/US/ /P
Two functions in one unit: Pump monitoring and pressure detection. Reliable diagnosis of disturbances in the suction area and detection of cavitation. Detection of outgassing liquids or trapped air in the pump. Independent system-pressure monitoring with second switching output. Pump control via analogue output
| Output signal: | switching signal; analogue signal; (configurable) | 
| Measuring range: | -1...10 bar -14.5...145 psi -0.1...1 MPa | 
| -1...10 bar: | -14.5...145 psi | 
| Process connection: | threaded connection G 1 external thread sealing cone | 
| Special feature: | Gold-plated contacts | 
| Application: | food and beverage industry | 
| Installation: | freely rotatable housing 350° | 
| Media: | viscous media and liquids with suspended particles; liquids and gases | 
| Medium temperature [°C]: | -25...125; (145 max. 1h) | 
| Min. bursting pressure: | 150 bar 2175 psi 15 MPa | 
| 150 bar: | 2175 psi | 
| Pressure rating: | 50 bar 725 psi 5 Mpa | 
| 50 bar: | 725 psi | 
| Type of pressure: | relative pressure; vacuum | 
| No dead space: | yes | 
| Operating voltage [V]: | 18...32 DC | 
| Current consumption [mA]: | < 50 | 
| Min. insulation resistance [MΩ]: | 100; (500 V DC) | 
| Protection class: | III | 
| Reverse polarity protection: | yes | 
| Power-on delay time [s]: | 0.2 | 
| Integrated watchdog: | yes | 
| Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 | 
| Total number of outputs: | 2 | 
| Output signal: | switching signal; analogue signal; (configurable) | 
| Electrical design: | PNP | 
| Number of digital outputs: | 2 | 
| Output function: | normally open / normally closed; (parameterisable) | 
| Max. voltage drop switching output DC [V]: | 2 | 
| Permanent current rating of switching output DC [mA]: | 250 | 
| Switching frequency DC [Hz]: | 350 | 
| Notes on switching frequency: | OUT2 | 
| Number of analogue outputs: | 1 | 
| Analogue current output [mA]: | 4...20, invertible; (scalable) | 
| Max. load [Ω]: | (Ub - 10 V) / 20 mA | 
| Short-circuit protection: | yes | 
| Type of short-circuit protection: | pulsed | 
| Overload protection: | yes | 
| Measuring range: | -1...10 bar -14.5...145 psi -0.1...1 MPa | 
| -1...10 bar: | -14.5...145 psi | 
| Set point SP: | -0.98...10 bar -14.2...145 psi -0.098...1 MPa | 
| -0.98...10 bar: | -14.2...145 psi | 
| Reset point rP: | -1...9.98 bar -14.5...144.7 psi -0.1...0.998 MPa | 
| -1...9.98 bar: | -14.5...144.7 psi | 
| Analogue start point: | -1...7.25 bar -14.5...105.1 psi -0.1...0.725 MPa | 
| -1...7.25 bar: | -14.5...105.1 psi | 
| Analogue end point: | 1.5...10 bar 21.8...145 psi 0.15...1 MPa | 
| 1.5...10 bar: | 21.8...145 psi | 
| In steps of: | 0.01 bar 0.1 psi 0.001 MPa | 
| 0.01 bar: | 0.1 psi | 
| Factory setting: | OU1 = Fnc OU2 = I ASP = 0.00 bar AEP = 10.00 bar | 
| Switch point accuracy [% of the span]: | < ± 0,2; (Turn down 1:1) | 
| Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) | 
| Characteristics deviation [% of the span]: | < ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) | 
| Linearity deviation [% of the span]: | < ± 0,15; (Turn down 1:1) | 
| Hysteresis deviation [% of the span]: | < ± 0,15; (Turn down 1:1) | 
| Long-term stability [% of the span]: | < ± 0,1; (Turn down 1:1; per year) | 
| Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,15; (0...70 °C) | 
| Temperature coefficient span [% of the span / 10 K]: | < ± 0,1; (0...70 °C) | 
| Response time [ms]: | < 2.5 | 
| Damping for the switching output dAP [s]: | 0...10 | 
| Damping for the analogue output dAA [s]: | 0...10 | 
| Step response time analogue output [ms]: | 0.2 | 
| Parameter setting options: | zero point; span | 
| Ambient temperature [°C]: | -25...80 | 
| Storage temperature [°C]: | -40...100 | 
| Protection: | IP 67; IP 69K | 
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V | 
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD | 
| EN 61000-4-3 HF radiated: | 10 V/m | 
| EN 61000-4-4 Burst: | 2 kV | 
| EN 61000-4-5 Surge: | 0,5/1 kV | 
| EN 61000-4-6 HF conducted: | 10 V | 
| Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) | 
| DIN IEC 68-2-27: | 50 g (11 ms) | 
| Vibration resistance: | DIN IEC 68-2-6 20 g (10...2000 Hz) | 
| DIN IEC 68-2-6: | 20 g (10...2000 Hz) | 
| MTTF [years]: | 188 | 
| Weight [g]: | 451.2 | 
| Materials: | stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE | 
| Materials (wetted parts): | ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE | 
| Min. pressure cycles: | 100 million | 
| Process connection: | threaded connection G 1 external thread sealing cone | 
| Display: | Display unit 4 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit | 
| Display unit: | 4 x LED, green | 
| switching status: | 2 x LED, yellow | 
| function display: | alphanumeric display, 4-digit | 
| measured values: | alphanumeric display, 4-digit | 
| Remarks: | pump diagnosis for pumps with constant rotational speed (+/- 10 % deviation of the taught rotational speed) speed range 40...3000 U/min minimum pressure for pump diagnosis 0,5 bar The 3-A qualification is only valid if adapters with 3-A qualification are used for installation. | 
| Pack quantity: | 1 pcs. | 
| Connection: | Connector: 1 x M12; Contacts: gold-plated | 
| ECCN: | |
| Kraj pochodzenia: | DE | 
| EAN: | |
| Waga: | 0,45 kg | 
| Długość: | 0,00 m | 
| Szerokość: | 0,00 m | 
| Wysokość: | 0,00 m |