N95004
I9-2003-N/M10X1/0,5M
Inductive NAMUR sensor. I9-2003-N/M10X1/0,5M
High pressure rating. Very high switching frequency. For connection to intrinsically safe circuits. Robust metal housing for use in harsh industrial environments
| Electrical design: | NAMUR |
| Output function: | normally closed |
| Housing: | threaded type |
| Dimensions [mm]: | M10 x 1 |
| Application: | housing suited for an ambient pressure of max. 100 bar |
| Installation: | installation on aluminium measuring wheel; (DN80) |
| Pressure rating [bar]: | 100 |
| Connection to switching amplifiers: | yes |
| Switching amplifiers: | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
| Nominal voltage DC [V]: | 8.2; (1kΩ) |
| Supply voltage DC [V]: | 7.5...30 |
| Current consumption [mA]: | < 1; (disabled; conductive: > 2,1) |
| Protection class: | III |
| Electrical design: | NAMUR |
| Output function: | normally closed |
| Permanent current rating of switching output DC [mA]: | 30 |
| Switching frequency DC [Hz]: | 2000 |
| Notes on switching frequency: | on the aluminium measuring wheel |
| Hysteresis [% of Sr]: | 1...15 |
| Ambient temperature [°C]: | -20...60 |
| Protection: | IP 67 |
| EMC: | EN 60947-5-6 |
| Shock/vibration resistance: | 30 g (11 ms) / 10-55 Hz (1 mm) |
| Max. internal capacitance [nF]: | 90 |
| Max. internal inductance [µH]: | 100 |
| Weight [g]: | 24.8 |
| Housing: | threaded type |
| Mounting: | non-flush mountable |
| Dimensions [mm]: | M10 x 1 |
| Thread designation: | M10 x 1 |
| Materials: | brass special coating; sensing face: LCP |
| Pack quantity: | 1 pcs. |
| Connection: | Cable: 0.5 m; 2 x 0.14 mm², PVC |
| ECCN: | |
| Kraj pochodzenia: | DEUTSCHLAND |
| EAN: | |
| Waga: | 0,02 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |