KI0061
Capacitive sensor. KI-2200NBBOA/2P
For the detection of liquids and dry bulk materials. With combined AC/DC output stage, adjustable switching delay. Two-wire technology
Output function: | normally closed |
Sensing range [mm]: | 20 |
Housing: | threaded type |
Dimensions [mm]: | M30 x 1.5 / L = 81 |
Operating voltage [V]: | 20...250 AC/DC |
Current consumption [mA]: | < 20 |
Protection class: | II |
Reverse polarity protection: | no |
Output function: | normally closed |
Max. voltage drop switching output DC [V]: | 8 |
Max. voltage drop switching output AC [V]: | 10 |
Minimum load current [mA]: | 5 |
Max. leakage current [mA]: | 2.5 (250 V AC) / 1.7 (110 V AC) / 1.5 (24 V DC) |
Permanent current rating of switching output AC [mA]: | 200; (350 (...50 °C)) |
Permanent current rating of switching output DC [mA]: | 200; (350 (...50 °C)) |
Short-time current rating of switching output [mA]: | 2200; (20 ms / 0,5 Hz) |
Switching frequency AC [Hz]: | 10 |
Switching frequency DC [Hz]: | 10 |
Short-circuit proof: | no |
Overload protection: | no |
Output holding time: | adjustable (0...60 s ) |
Sensing range [mm]: | 20 |
Sensing range adjustable: | yes |
Factory setting sensing range [mm]: | 20 |
Real sensing range Sr [mm]: | 20 ± 10 % |
Hysteresis [% of Sr]: | 1...15 |
Switch point drift [% of Sr]: | -20...20 |
Ambient temperature [°C]: | -25...80 |
Note on ambient temperature: | temperature of the sensing face: -25...110 |
Protection: | IP 65; IP 67 |
EMC: | EN 61000-4-2 ESD 25 kV CD / 30 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5 kV line to line, Ri: 2 Ohm EN 61000-4-6 HF conducted 3 V EN 55011 class B |
EN 61000-4-2 ESD: | 25 kV CD / 30 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-5 Surge: | 0,5 kV line to line, Ri: 2 Ohm |
EN 61000-4-6 HF conducted: | 3 V |
EN 55011: | class B |
Vibration resistance: | (10...55 Hz) / 1 mm amplitude, oscillation period 5 min., 30 min. per axis at resonance or 55 Hz |
Shock resistance: | 30 g 6 shocks / 11 ms half-sine (x, y, z) |
MTTF [years]: | 221.4 |
Weight [g]: | 186.5 |
Housing: | threaded type |
Mounting: | non-flush mountable |
Dimensions [mm]: | M30 x 1.5 / L = 81 |
Thread designation: | M30 x 1.5 |
Materials: | PBT |
Display: | switching status 1 x LED, yellow |
switching status: | 1 x LED, yellow |
Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
Accessories (supplied): | lock nuts: 2 screwdriver: 1 |
Remarks: | Recommendation: Check the safe functioning of the unit after a short circuit. |
Pack quantity: | 1 pcs. |
Connection: | Cable: 2 m, PVC; 2 x 0.5 mm² |
ECCN: | |
Kraj pochodzenia: | DE |
EAN: | |
Waga: | 0,19 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |