IN0097
Inductive sensor. IN-2002-ABOA
With combined AC/DC output stage. Large operating voltage range. Two-wire technology. Particularly space-saving rectangular housing. For use where space is restricted
| Output function: | normally open | 
| Sensing range [mm]: | 2 | 
| Housing: | rectangular | 
| Dimensions [mm]: | 40 x 12 x 26 | 
| Operating voltage [V]: | 20...250 AC/DC | 
| Protection class: | II | 
| Reverse polarity protection: | yes | 
| Output function: | normally open | 
| Max. voltage drop switching output DC [V]: | 6 | 
| Max. voltage drop switching output AC [V]: | 6.7 | 
| Minimum load current [mA]: | 5 | 
| Max. leakage current [mA]: | 2.0 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC) | 
| Permanent current rating of switching output AC [mA]: | 250; (350 (...50 °C)) | 
| Permanent current rating of switching output DC [mA]: | 100 | 
| Short-time current rating of switching output [mA]: | 2200; (50 ms / 1 Hz) | 
| Switching frequency AC [Hz]: | 25 | 
| Switching frequency DC [Hz]: | 50 | 
| Short-circuit proof: | no | 
| Overload protection: | no | 
| Sensing range [mm]: | 2 | 
| Real sensing range Sr [mm]: | 2 ± 10 % | 
| Operating distance [mm]: | 0...1.6 | 
| Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.25 / aluminium: 0.2 / copper: 0.05 | 
| Hysteresis [% of Sr]: | 1...20 | 
| Switch point drift [% of Sr]: | -10...10 | 
| Ambient temperature [°C]: | -25...80 | 
| Protection: | IP 67 | 
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 3 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 3 V EN 55011 emission class B | 
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD | 
| EN 61000-4-3 HF radiated: | 3 V/m | 
| EN 61000-4-4 Burst: | 2 kV | 
| EN 61000-4-6 HF conducted: | 3 V | 
| EN 55011 emission: | class B | 
| MTTF [years]: | 609 | 
| Weight [g]: | 104.8 | 
| Housing: | rectangular | 
| Mounting: | flush mountable | 
| Dimensions [mm]: | 40 x 12 x 26 | 
| Materials: | PBT | 
| Display: | switching status 1 x LED, yellow | 
| switching status: | 1 x LED, yellow | 
| Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting | 
| Remarks: | Recommendation: Check the safe functioning of the unit after a short circuit. | 
| Pack quantity: | 1 pcs. | 
| Connection: | Cable: 2 m, PVC; 2 x 0.5 mm² | 
| ECCN: | |
| Kraj pochodzenia: | DE | 
| EAN: | |
| Waga: | 0,10 kg | 
| Długość: | 0,00 m | 
| Szerokość: | 0,00 m | 
| Wysokość: | 0,00 m |