IM002A
Inductive sensor. IME2040-FBOA/3D
For applications in hazardous areas. With combined AC/DC output and two-wire technology. Output function normally open / normally closed programmable. Robust housing for use in harsh industrial environments. Five positions of the sensing face selectable
Output function: | normally open / normally closed; (selectable) |
Sensing range [mm]: | 40 |
Housing: | rectangular |
Dimensions [mm]: | 40 x 40 x 105 |
Operating voltage [V]: | 20...250 AC/DC |
Protection class: | II |
Reverse polarity protection: | no |
Output function: | normally open / normally closed; (selectable) |
Max. voltage drop switching output DC [V]: | 6 |
Max. voltage drop switching output AC [V]: | 6.5 |
Minimum load current [mA]: | 5 |
Max. leakage current [mA]: | 2.5 (250 V AC) / 1.3 (130 V AC) / 0.8 (24 V DC) |
Permanent current rating of switching output AC [mA]: | 150 |
Permanent current rating of switching output DC [mA]: | 100 |
Short-time current rating of switching output [mA]: | 2200; (20 ms / 0,5 Hz) |
Switching frequency AC [Hz]: | 10 |
Switching frequency DC [Hz]: | 10 |
Notes on switching frequency: | only for resistive loads; 2 Hz for utilisation category AC-140 |
Short-circuit proof: | no |
Overload protection: | no |
Sensing range [mm]: | 40 |
Real sensing range Sr [mm]: | 40 ± 10 % |
Operating distance [mm]: | 0...32.4 |
Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
Hysteresis [% of Sr]: | 1...20 |
Switch point drift [% of Sr]: | -10...10 |
Ambient temperature [°C]: | -20...60 |
Protection: | IP 65; IP 67 |
ATEX marking: | II 3D Ex tc IIIC T95°C Dc X |
EMC: | EN 60947-5-2 |
MTTF [years]: | 554 |
Weight [g]: | 253 |
Housing: | rectangular |
Mounting: | non-flush mountable |
Dimensions [mm]: | 40 x 40 x 105 |
Materials: | PC; PA; stainless steel |
Display: | switching status 1 x LED, yellow |
switching status: | 1 x LED, yellow |
Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
Remarks: | Recommendation: Check the safe functioning of the unit after a short circuit. 5 positions of the active zone possible |
Pack quantity: | 1 pcs. |
Connection: | terminals: 0.34...2.5 mm²; Cable sheath: Ø 5...9 mm |
ECCN: | |
Kraj pochodzenia: | RO |
EAN: | |
Waga: | 0,25 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |