II001A
Inductive sensor. IIA2015-ABOA/6M/3D
For applications in hazardous areas. With combined AC/DC output stage. Large operating voltage range. Two-wire technology. Robust metal housing for use in harsh industrial environments
| Output function: | normally open |
| Sensing range [mm]: | 15 |
| Housing: | threaded type |
| Dimensions [mm]: | M30 x 1.5 / L = 81 |
| Installation: | use in hazardous areas only with installed protective cover |
| Operating voltage [V]: | 20...250 AC/DC |
| Protection class: | II |
| Reverse polarity protection: | yes |
| Output function: | normally open |
| Max. voltage drop switching output DC [V]: | 6 |
| Max. voltage drop switching output AC [V]: | 6.5 |
| Minimum load current [mA]: | 5 |
| Max. leakage current [mA]: | 2.5 (250 V AC) / 1.3 (130 V AC) / 0.8 (24 V DC) |
| Permanent current rating of switching output AC [mA]: | 150 |
| Permanent current rating of switching output DC [mA]: | 100 |
| Short-time current rating of switching output [mA]: | 2200; (20 ms / 0,5 Hz) |
| Switching frequency AC [Hz]: | 25 |
| Switching frequency DC [Hz]: | 50 |
| Notes on switching frequency: | only for resistive loads; 2 Hz for utilisation category AC-140 |
| Short-circuit protection: | no |
| Overload protection: | no |
| Sensing range [mm]: | 15 |
| Real sensing range Sr [mm]: | 15 ± 10 % |
| Operating distance [mm]: | 0...12.1 |
| Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
| Hysteresis [% of Sr]: | 1...20 |
| Switch point drift [% of Sr]: | -10...10 |
| Ambient temperature [°C]: | -20...60 |
| Protection: | IP 67 |
| ATEX marking: | II 3D Ex tc IIIC T80°C Dc X |
| EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 3 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 3 V IEC 60255-5 1 kV line to line, Ri: 500 Ohm EN 55011 emission class B |
| EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
| EN 61000-4-3 HF radiated: | 3 V/m |
| EN 61000-4-4 Burst: | 2 kV |
| EN 61000-4-6 HF conducted: | 3 V |
| IEC 60255-5: | 1 kV line to line, Ri: 500 Ohm |
| EN 55011 emission: | class B |
| MTTF [years]: | 607 |
| Weight [K40]: | 489 |
| Housing: | threaded type |
| Mounting: | non-flush mountable |
| Dimensions [mm]: | M30 x 1.5 / L = 81 |
| Thread designation: | M30 x 1.5 |
| Materials: | brass white bronze coated; sensing face: PBT; lock nuts: brass white bronze coated; Protective cover: PA |
| Display: | switching status 1 x LED, yellow |
| switching status: | 1 x LED, yellow |
| Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
| Accessories (supplied): | lock nuts: 3 Protective cover: 1 |
| Remarks: | Recommendation: Check the safe functioning of the unit after a short circuit. |
| Pack quantity: | 1 pcs. |
| Connection: | Cable: 6 m, PVC; 2 x 0.50 mm² |
| ECCN: | |
| Kraj pochodzenia: | RO |
| EAN: | |
| Waga: | 0,49 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |