KL2612
KL2612 | 2-channel relay output terminal
The KL2612 output terminal switches two relays, each having one changeover contact, under control of the automation device. It has potential-free contacts. The power contacts are not looped through.
| Number of outputs: | 2 x change-over |
| Nominal voltage: | 125 V AC/30 V DC |
| Load type: | ohmic |
| Max. output current: | 2 A per channel |
| Switching current: | 0.5 A AC/2 A DC (ohmic) |
| Ohmic switching current: | 0.5 A AC/2 A DC |
| Inductive switching current: | no data |
| Minimum permitted load: | 10 µA at 10 mV |
| Lamp test, electronic ballast: | max. 2 A starting current |
| Electrical isolation: | 500 V (K-bus/field potential) |
| Current consumption power contacts: | – |
| Current consumption K-bus: | typ. 60 mA |
| Bit width in the process image: | 2 outputs |
| Operating cycles mech. (min.): | 1 x 108 |
| Operating cycles electr. (min.): | 2 x 105 (1 A/30 V DC) |
| Configuration: | no address or configuration setting |
| Special features: | signal relay |
| Weight: | approx. 80 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all KSxxxx Bus Terminals |
| Approvals: | CE, UL, Ex, GL |
| ECCN: | |
| Kraj pochodzenia: | |
| EAN: | |
| Waga: | 0,00 kg |
| Długość: | 0,00 m |
| Szerokość: | 0,00 m |
| Wysokość: | 0,00 m |