EL6900
EL6900 | TwinSAFE Logic
TwinSAFE enables networks with up to 1,024 TwinSAFE devices. The TwinSAFE Logic can establish 128 connections to other TwinSAFE devices. Multiple EL6900 are cascadable within a network. The EtherCAT Terminal features certified safety function blocks, which are configured according to the application to be realised. Safety functions such as emergency stop, safety door monitoring, two-hand control, etc. can thus easily be selected and linked. All blocks can be freely connected among each other and are complemented by operators such as AND, OR, etc. The required functions are configured via the TwinCAT System Manager and loaded into the EL6900 TwinSAFE Logic via the fieldbus.
Specification: | link unit between safe input and output signals |
Protocol: | TwinSAFE/Safety over EtherCAT |
Cycle time: | approx. 500 µs/according to project size |
Fault response time: | ≤ watchdog time (parameterisable) |
Current consumption power contacts: | – |
Current consumption E-bus: | typ. 188 mA |
Installation position: | horizontal |
Safety standard: | DIN EN ISO 13849-1:2008 (Cat. 4, PL e) and EN 61508:2010 (SIL 3) |
Weight: | approx. 50 g |
Protection class: | IP 20 |
Approvals/markings: | Overview of TwinSAFE Certifications (PDF) |
Ex-Marking: | II 3 G Ex nA IIC T4 Gc |
Download EtherCAT slave information (ESI): | ESI config file ELx9xx (ZIP) |
ECCN: | |
Kraj pochodzenia: | |
EAN: | |
Waga: | 0,00 kg |
Długość: | 0,00 m |
Szerokość: | 0,00 m |
Wysokość: | 0,00 m |